Safety device
Compressor and fans are equipped with thermal protectors that prevent from overcurrent and overvoltage
Condensate discharge
Air conditioners are designed so that condensate drain is directly discharged into the environment, through a passage in the tank. It
is very important to control, that condensate evacuation is not clogged. A copper tube is provided with the air conditioner.
COMMISSIONING
After finishing assembly of conditioner, wait approx. 30 min. before starting it up (the oil must collected in the compressor to ensure
lubrication).
Unit is setted at 35°C.
This setting may be varied by turning the setting screw with a small screwdriver as indicated in the figure. To gain access to the
thermostat remove the covering panel.
In order not to compromise reliability of the unit, set point must not exceed 40°C. It is advised not to set thermostat at less
than 25°C to avoid dangerous vapor condensation on inside components if the door is opened, this occurs most frequently
in tropical climates.
-High temperature thermostat in the control panel: this provides a voltage-free contact in the terminal board an alarm signal which
indicates that the alarm level inside the control panel has been reached. It is factory set at 55°C but may be easily set at other
temperatures
Once the unit is installed :
MAINTENANCE
Cooling circuit consists of an hermetically sealed system and requires no maintenance it is factory filled with expected quantity of
gas. Then a leak test is performed as well as complete function test. Fans do not require maintenance, they are mounted on ball
bearings, protected against humidity and dust, and equipped on thermal protector. Expected life is 30,000 hours. Only external fan,
according to degree of impurity which they are subjected, must be periodically cleaned with compressed air. Use of filter is
appropriate if there are impurities in the air. Warning "before beginning of any maintenance, disconnect power supply."
SUPPLY
Conditioner is delivered packed with :
- Gasket
- Technical manual
- Keys
For any help, do not hesitate to Contact customer service :
-Give power to the unit using the external mains switch.
-The evaporator fan will start immediately.
-If temperature inside the control panel is higher than thermostat setting, the condenser fan and
compressor will also start.