Wrong use
The conditioner must not be used:
in conditions other than those indicated
-
in an explosive atmosphere, aggressive or with high concentration of dust or oily substances in the air
-
if the condensates do not flow
-
without cover panels.
-
HANDLING AND TRANSPORT
During shipment, air conditioners are protected by high strength cartons on pallets. Displacement and storage must be done
maintaining vertical position and avoiding, bumps and blows.
If the unit has travelled or has been stored in a different position from that intended, it is important, after installation, to
wait at least 24 hours before start-up.
In order to help for operations, installation, units are provided with eyebolts. When receipt, check packaging is intact and check any
damage caused by transport. Traces of oil on packaging should indicate refrigerant leak, therefore refrigeration system is no longer
hermetically sealed.
ASSEMBLY
Before proceeding to assembly take care that:
installation position of the cabinet and therefore of the conditioner provide good ventilation conditions;
-
installation site is not dirty or humid;
-
electric power is appropriate to characteristics indicated on nameplate;
-
ambient temperature does not exceed + 55 °C;
-
cabinet is fully sealed;
-
respect minimum space around the unit
-
inlet and outlet air are not obstructed;
-
circuit is fitted in vertical position with maximum tilt of 2°;
-
send connection for condensates evacuation;
-
electrical connection are done by qualified authorized technician.
-
to avoid accumulation of condensate, a switch is fitted on the door in order to stop conditioner
-
operating in case of opened door.
Important: To ensure durable fixation, the mounting surface between conditioner and cabinet should be
reinforced in necessary.
Condensate evacuation :
Condensate evacuation is done under air conditioner by a threaded sleeve male 3/4.
Fixing conditioner
1) Predispose the fixing holes, the supplied cable hole and loopholes of circulation of the air on the panel of the enclosure, as
drilling templates in appendix to the manual shown. Ensure that nothing should prevent positioning of gasket between cabinet
and conditioner
2) Apply the gasket on back panel of the conditioner
3) Fix the conditioner on right position, using screws M6x20mm and washers (NOT supplied)
ELECTRICAL CONNECTION
Supply voltage and frequency must be in conformity with nameplate of the unit. The air conditioner must be connected to the network with
appropriate switch. None additional thermostat should be connected
TECHNICAL INFORMATION
The conditioner is made of 3 main components: compressor, evaporator, condenser. This cooling circuit is unloaded with a low
boiling point cooling fluid. Cooling fluid is R134a (CH2FCF3), without chlorine. Its ozone aggression capability is zero, do that
cooling fluid used is ecological. A dryer filter, offers efficient protection from humidity, acids, impure particles inside frigorific circuit.
3)
2)
Electrical enclosure
Conditioner's position
1)