Combustible Finish; Trim Installation - Kozy Heat Fireplaces Callaway-72 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.2 Combustible Finish

3.2.1 Trim Installation

NOTE: It is not required to use the #KZK-072 discharge trim if desired to
run finishing material up to the finishing material standoff. Finishing
material must not block the opening and must be run evenly along the
plenum opening.
WARNING! RISK OF OVERHEATING AND FIRE! Ensure the KZK duct
system is installed in accordance to this manual AND the convection
baffle is removed when using these combustible clearances.
DRYWALL STOPS AT FINISHING MATERIAL STAND OFFS
AROUND KZK DISCHARGE OPENING. DISCHARGE TRIM
COVERS THESE EDGES COMPLETELY.
COMBUSTIBLE MATERIAL
DISCHARGE TRIM
¼
3
"
(83mm)
Figure 3.3, Drywall Finish
UP TO 1" (25mm) THICK COMBUSTIBLE MATERIAL UP TO EDGE
OF DISCHARGE TRIM. 1" (25mm) COMBUSTIBLE MATERIAL CANNOT GO
CLOSER TO DISCHARGE OPENING. 1" (25mm) COMBUSTIBLE MATERIAL
GOES ON TOP OF ANY REQUIRED NON-COMBUSTIBLE MATERIAL
REQUIRED ON THE FIREPLACE.
COMBUSTIBLE MATERIAL
UP TO 1" (25mm) THICK
DISCHARGE TRIM
4
"
(104mm)
Figure 3.4, Combustible Finish Material up to 1" Thick
10
Figure 3.5, Non-combustible Material Trim Finish
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
NON-COMBUSTIBLE MATERIALS, SUCH AS TILE OR STONE,
UP TO THE AIR DISCHARGE OPENING. MINIMUM AIR
DISCHARGE OPENING MUST BE MAINTAINED THE ENTIRE
LENGTH OF AIR DISCHARGE OPENING.
DISCHARGE TRIM IS OPTIONAL FOR THIS INSTALLATION.
NON-COMBUSTIBLE MATERIAL
UP TO DISCHARGE OPENING
¼
2
"
(57mm)
Komfort Zone Kit #KZK-072