Note: This connection is optional.
8 . B A T T E R Y
The battery is the only UPS component which is not in permanent use. It has a useful life
of approximately 3 to 5 years. However, frequent major discharges or exposure to
temperatures over 20C will shorten its life span. We therefore recommend that users
recharge the battery once every 3 months when the unit is not in use in order to
compensate for natural discharging. UPS backup time will depend on the powered load,
as well as the age and condition of the batteries.
WARNING!
Batteries should always be replaced by qualified technicians. Batteries have a very
high short circuit current: connection errors could cause electric arcs resulting in
serious burns.
9 . T R O U B L E S H O O T I N G
Should the UPS fail to function correctly we recommend you perform the following tests
before calling the Hot Line.
PROBLEM
No LED display on
front panel.
In the event of power
failure, backup time is
shortened.
Mains normal but the
unit is on battery mode
(LED is flashing)
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 12 10 AA 59 204 07
POSSIBLE CAUSE
Low battery.
Faulty battery.
UPS is not turned on.
UPS overload.
Battery voltage is too low.
Battery defect due to high
temperature operating
environment, or improper
use of battery.
Fuse is broken.
Loose power cord.
SOLUTIONS
Charge battery for up to 8 hours.
Replace with the same type of battery.
Press the power switch again to turn
on the UPS.
Remove some non-critical load.
Charge battery up to 8 hours.
Replace with the same type of battery.
Replace Fuse
Connect the power cord properly.
7