CALIBRATION OF VULCANIZING MOLD
This vulcanizer mold has a thermostat mounted on rear of bottom mold half
under wiring cover. To recalibrate thermostat, remove wiring cover by removing
screw at each side. Twist cover back away from mold press.
Open mold wide so both halves are pressed together. Check temperature with
TEMPIL -STIK or pyrometer. Adjust thermostat as required. T urning adjustment
screw clockwise reduces temperature. Counterclockwise increases temperature.
!
Be careful not to touch live electrical parts when cover is removed. Replace
cover after calibration.
ACCESSORY ITEMS FOR USE IN VULCANIZING INSULATOR
TO CABLE
Tempil-Stik
100823-3
325°F
100823-4
350°F
CABLE BUSHING
Cable Data
ITT EXANE SURPRENANT
CABLE
Part Number
MCM Size
201117-1
313
201117-2
535
201117-3
646
201117-4
777
SPARE OR REPLACEMENT PART FOR VULCANIZER MOLDS
See bill of material on vulcanizer assembly drawing for part numbers. Order by
part number and description (for example to order thermo switch for A300087
order 100566-1 thermo switch).
MISCELLANEOUS SPARE PARTS
100566-1
Thermo Switch
200704-2
Heater
100827-4
Pilot light, Amber
100827-3
Pilot light, Red
VULCANIZER KITS
A300087-1
313 MCM, ITT Exane Cable
A300087-2
535 MCM, ITT Exane Cable
A300087-3
646 MCM, ITT Exane Cable
A300087-4
777 MCM, ITT Exane Cable
Note that insulators are color-coded for circuit identification. Be careful to
assemble correct insulator on correct cable.
RIG-UP PROCEDURE
A. When setting up an installation, check to be sure that all power is turned
off and locked out. Begin at power source, plug female cable connector
(machine side), into male connector or receptacle. Be careful to maintain
circuit identification. Mate like colors, phases or polarities.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms
and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
CAUTION
Cable O.D. -
2000V
0.960
1.235
1.335
1.405
Eaton's Crouse-Hinds Division
1201 Wolf Street Syracuse, NY 13208 • U.S.A.
Copyright© 2015
MAINTENANCE
We recommend a maintenance program as described per maintenance
sheet MS1777 .
IF 1778
Revision 2
Revised 12/15