Lindab LT 600 Mode D'emploi page 10

Testeur d'étanchéité
Masquer les pouces Voir aussi pour LT 600:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

About the chart:
The bar chart shows the permitted leakage flow rate for the airtightness classes, with the specified m² and the actual
test pressure . The test value appears as a red line .
Compliant airtightness classes are shown with green bars . Non-compliant classes are shown with red bars .
10
manual-LTEST-1082_EN-DE-FR-SE.indd 10
Shows the configured parameter and the maximum permitted leakage flow
rate .
• Press the  to start the test .
• A self test is carried out before the test starts .
• The test starts once the selected pressure is reached, and continues for
five minutes .
• You can interrupt the test at any time by pressing Stop .
While the test is running, the achieved pressure and the current flow rate
are displayed .
• After the test duration of 300 s, the device stops automatically . (Stand-
ardised test duration) If you press Stop to end the test early, the results
are displayed .
• The device indicates whether the test has passed or failed with the
specified parameters .
• Press the Print key to print the report or press the New key to start a
new test .
Viewing the report before printing .
• You can use the  or  key to scroll through the report .
• Switch on the TD 600 printer and place it close to the IR window .
• Press OK to start printing .
• Note: The report is not permanently stored unless you select "Save" on
the menu .
Chart:
• Press the MENU key and press the  or  key to select Chart from the
menu .
• Confirm by pressing the  key .
• You can print the chart by pressing the Print key on the TD 600 .
• To return to the menu press the Menu or New key once .
• To start a new test, press the Menu key twice .
2012-03-28 12:32:39

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ltest

Table des Matières