2. INDOOR UNIT INSTALLATION

2-1. ATTACHING THE INSTALLATION PLATE
• Find a stud in the wall to attach installation plate (1) horizontally by tightening the fixing
screws (2) firmly.
• To prevent installation plate (1) from vibrating, be sure to install the attachment screws
in the holes indicated in the illustration. For added support, additional screws may also
be installed in other holes.
• If the recessed bolt is too long, change it for a shorter one (field-supplied).
2-2. DRILLING
1) Determine where the holes will be located on the wall.
2) Drill a ø 3 in. (75 mm) hole. The outdoor side should be 6/32 to 9/32 in. (5 to 7 mm)
lower than the indoor side.
3) Insert wall hole sleeve (C).
2-3. CONNECTING WIRES FOR INDOOR UNIT
Note:
When the indoor unit is powered from the outdoor unit, depending on local code, a discon-
nect switch needs to be installed to a power supply circuit.
1) Open the front panel.
2) Place the upper part of the indoor unit on the installation plate.
3) Remove electrical cover.
4) Remove VA clamp.
5) Remove corner box.
6) Remove cable guide.
7) Remove conduit plate.
8) Attach conduit pipe (for rear piping) / elbow joint (for right, left, or downward piping) to
conduit plate with lock nut. The thread of the installed conduit pipe / elbow joint appear-
ing inside should be less than 3/8 in. (10 mm). (Fig. 1) Elbow joint should appear less
than 1-3/16 in. (30 mm) outside. (Fig. 2)
9) Process the end of ground wire (Fig. 3). Connect it to the ground terminal of electrical
parts box.
10) Process the end of indoor/outdoor unit connecting wire (A) (Fig.3). Attach it to the
terminal block. Be careful not to make mis-wiring. Attach the wire to the terminal block
securely so that its core cannot be seen, and no external force affects the connecting
section of the terminal block.
11) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fas-
tened.
12) Reinstall conduit plate.
13) Reinstall cable guide.
14) According to the piping direction, remove the shaded part of the left side of box (Fig.4)
or corner box (Fig. 5).
15) Reinstall VA clamp.
16) Reinstall electrical cover.
17) Reinstall panel assembly.
Remark:
* A disconnect switch should be
required.
Check the local code.
** Use a ring tongue terminal in
order to connect a ground wire
to terminal.
208/230 V AC
1phase, 60 Hz
OUTDOOR UNIT
Power supply
208/230 V AC,
1phase 2 wires,
60 Hz
Ground
INDOOR UNIT
Grounding
Terminal block
terminal**
Disconnect
switch*
Grounding terminal**
Installation plate (1)
Level
4-11/16 in.
Wall
(120 mm)
or more
Attachment screw (2)
ø 3 in.
(75 mm)
Electrical cover
VA Clamp
Indoor
terminal
block
Cable guide
Conduit plate
Lock nut
• Connect wires to the appropri-
ate terminals
• For future servicing, leave some
slack in the connecting wires.
Conduit plate
Less than 3/8 in.
(10 mm)
Lock nut
Conduit pipe or
elbow joint
Fig. 1
5/8 in.
(15 mm)
2-3/16 in.
(55 mm)
Lead
wire
• Make ground wire a little longer than
others. (More than 1-9/16 in. [40 mm])
Fig. 3
Corner box
Remove panel for
Remove panel
piping on bottom
for piping on right
side of unit
side of unit
Fig. 5
2-13/16 in. (70 mm) or more
Ceiling
5-1/8 in. (130 mm) or more for left
and left back piping (using spacer)
4 in.
8-11/16 in.
(100 mm)
(220 mm)
or more
Insert
Align the
the
Center of
scale with
scale. *
ø 3 in.
the line. *
(75 mm)
hole
* Same for left hole.
Wall
6/32-9/32 in.
(5-7 mm)
Outdoor side
Pull tab to remove cable guide.
Electrical box
Grounding
terminal
Conduit pipe
or
Elbow joint
Conduit plate
Less than 1-3/16 in.
(30 mm)
Elbow joint
(for right, left, or downward piping)
Fig. 2
Box
Remove panel
for piping on
Remove panel for piping
left side of unit
on bottom left side of unit
Fig. 4
Wall