Danfoss EKC 531D1 Instructions page 5

Masquer les pouces Voir aussi pour EKC 531D1:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Step 4 (M&M operation)
Step 5 (M&M operation)
Step 6 (M&M operation)
Step 7 (M&M operation)
Step 8 (M&M operation)
Step 9 (M&M operation)
Step 10 (M&M operation)
Step 11 (M&M operation)
Step 12 (M&M operation)
Defi nition of condenser:
1-8: Total number of fan relays
9: Only via analog output and start of
frequency converter
Proportinal band Xp for (P= 100/Xp) con-
denser regulation
I: Integration time Tn for condenser regula-
tion
Alarm
Delay time for a "Saux1" alarm
Low alarm and safety limit for P0
Delay time for a DI1 alarm
Delay time for a DI2 alarm
Delay time for a DI3 alarm
Upper alarm and safety limit for Pc
Upper alarm limit for sensor "Saux1"
Miscellaneous
Controllers address
On/off switch (service-pin message)
Access code
Used sensor type for Sc3, Sc4 and "Saux1"
0=PT1000, 1=PTC1000
2-7=variations with temperature sensor
on P0 and Pc. See earlier in the manual.
Set supply voltage frequency
Manual control of outputs:
0: No override
1-10: 1 will cut in relay 1, 2 relay 2, etc.
11-18: Gives voltage signal on the analog
output. (11 gives 1.25 V, and so on in steps
of 1.25 V
P0 pressure transmitter's working range
- min. value
P0 pressure transmitter's working range
- max. value
Use of DI4-input
0=not used. 1=P0 displacement. 2=alarm
function. Alarm="A31"
Operating hours of relay 1 (value time
1000)
Operating hours of relay 2 (value time
1000)
Operating hours of relay 3 (value time
1000
Operating hours of relay 4 (value time
1000)
Setting of refrigerant
1=R12. 2=R22. 3=R134a. 4=R502.
5=R717. 6=R13. 7=R13b1. 8=R23.
9=R500. 10=R503. 11=R114. 12=R142b.
13=User defi ned. 14=R32. 15=R227.
16=R401A. 17=R507. 18=R402A.
19=R404A. 20=R407C. 21=R407A.
22=R407B. 23=R410A. 24=R170.
25=R290. 26=R600. 27=R600a. 28=R744.
29=R1270. 30=R417A
Use of DI5-input
0=not used. 1=Pc displacment. 2=alarm
function. Alarm="A32"
Pc pressure transmitter's working range
- min. value
EKC 531D1
c20
0
15
0
c21
0
15
0
c22
0
15
0
c23
0
15
0
c24
0
15
0
c25
0
15
0
c26
0
15
0
c27
0
15
0
c28
0
15
0
c29
0/OFF 9
0
n04
0.2 K
40 K
10
n05
30 s
600 s
150
A03 0 min. 90 min 30
A11 -99°C
30°C
-10
600 s
A27 1 s
600
/off
600 s
A28 1 s
600
/off
600 s
A29 1 s
600
/off
A30 -10 °C
99 °C
60.0
0 °C
A32
140°C
0.0
/off
o03* 1
60
o04* -
-
o05
off (-1) 100
o06
0
7
0
o12
50 Hz
60 H
0
o18
0
18
0
o20
-1 bar
0 bar
-1.0
o21
1 bar
40 bar 12.0
o22
0
2
0
o23
0.0 h
99.9 h 0.0
o24
0.0 h
99.9 h 0.0
o25
0.0 h
99.9 h 0.0
o26
0.0 h
99.9 h 0.0
o30
0
30
0
o37
0
2
0
o47
-1 bar
0 bar
-1.0
Instructions RI8HU352 © Danfoss 12/2004
Pc pressure transmitter's working range
- max. value
Read temperature at sensor "Saux1"
Operating hours of relay 5 (value time
1000)
Operating hours of relay 6 (value time
1000)
Operating hours of relay 7 (value time
1000)
Operating hours of relay 8 (value time
1000)
Service
Read temperature at sensor "Sc3"
Read temperature at sensor "Sc4"
*) This setting will only be possible if a data communication moduel has
been installed in the controller.
The controller can give the following messages
E1
Error
Fault in controller
message
E2
Regulation is outside the range, or the control
signal is defective
A2
Alarm
Low P0
message
A11
Refrigerant not selected
A17
High Pc
A19
DO 1 alarm. Terminal 29 is open
A20
DO 2 alarm. Terminal 30 is open
A21
DO 3 alarm. Terminal 31 is open
A22
DO 4 alarm. Terminal 32 is open
A23
DO 5 alarm. Terminal 33 is open
A24
DO 6 alarm. Terminal 34 is open
A25
DO 7 alarm. Terminal 35 is open
A26
DO 8 alarm. Terminal 36 is open
A27
Room temperature alarm (housing temp.)
A28
DI 1 alarm. Terminal 46 interrupted
A29
DI 2 alarm. Terminal 47 interrupted
A30
DI 3 alarm. Terminal 49 interrupted
A31
DI 4 alarm. Terminal 50 interrupted
A32
DI 5 alarm. Terminal 52 interrupted
A45
Regulation stopped
S2
Status
Wait for "c01"
message
S5
Wait for "c07"
S8
Wait for "c11" or "c12"
S9
Wait for "c14" or "c15"
S10
Refrigeration stopped by the internal or external
start/stop function
PS
Info
Access code is required before you have access to
the settings
o48
1 bar
60 bar 34.0
o49
0.0 °C
°C 22.4
o50
0.0 h
99.9 h 0.0
o51
0.0 h
99.9 h 0.0
o52
0.0 h
99.9 h 0.0
o53
0.0 h
99.9 h 0.0
u44
°C 23.5
u45