Regulation parameter for ++ Zone
Regulation parameter for - Zone
Regulation parameter for - Zone
Regulation parameter for - - Zone
Definition of compressor connections.
See options on page 3
Definition of condenser:
1-4: Total number of fan relay
5-8: Not used
9: Only via analog output and start of frequency converter
10: Not used
11- 14: Total number of fan relays (1-4) which are to be connected with
alternating start-up.
Cut in compressor capacity with manual control. See also "c32"
Manual control of compressor capacity (when ON, the value in "c31" will
be used)
Pump down limit. Limit value where the last compressor is cut out.
Proportinal band Xp for (P= 100/Xp) condenser regulation
I: Integration time Tn for condenser regulation
Cutin condenser capacity with manual control. See also "n53"
Manual control of condenser capacity (when ON, the value in "n52" will
be used)
Start speed The voltage for the speed regulation is kept at 0V until the
regulation requires a higher value than the value set here.
Min. speed. The voltage for the speed regulation switches to 0V when the
regulation requires a lower value than the value set here.
Alarm
Delay time for a A32 alarm
Low alarm and safety limit for P0
Delay time for a DI1 alarm
Delay time for a DI2 alarm
Delay time for a DI3 alarm
Upper alarm and safety limit for Pc
Upper alarm limit for sensor "Saux1"
Delay time for a P0 alarm
Delay time for a Pc alarm
Miscellaneous
Controllers address
On/off switch (service-pin message)
Access code
Used sensor type for Sc3, Sc4 and "Saux1"
0=PT1000, 1=PTC1000
2-7=variations with temperature sensor on P0 and Pc. See manual.
Set supply voltage frequency
Manual control of outputs:
0: No override
1-10: 1 will cut in relay 1, 2 relay 2, etc.
11-18: Gives voltage signal on the analog output. (11 gives 1.25 V, and so
on in steps of 1.25 V
P0 pressure transmitter's working range - min. value
P0 pressure transmitter's working range - max. value
Use of DI4-input
0=not used. 1=P0 displacement. 2=alarm function. Alarm="A31"
Operating hours of relay 1 (value time 1000)
Operating hours of relay 2 (value time 1000)
Operating hours of relay 3 (value time 1000
Operating hours of relay 4 (value time 1000)
Setting of refrigerant
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23.
9=R500. 10=R503. 11=R114. 12=R142b. 13=User defined. 14=R32.
15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C.
21=R407A. 22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600.
27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A.
* this setting is only possible if data communication module is mounted in the controller
6
Instructions RI8NM252 © Danfoss 12/2009
c12
0.1 min.
c13
0.1 K / 0.1 bar
c14
0.1 min.
c15
0.02 min.
c16
1
c29
0/OFF
c31
0%
c32
OFF
c33
-99.9°C / -1.0 bar 100°C / 60 bar
n04
0.2 K / 0.2 bar
n05
30 s
n52
0%
n53
OFF
n54
0%
n55
0%
A03
0 min.
A11
-99°C / -1.0 bar
A27
0 min. (-1=OFF)
A28
0 min. (-1=OFF)
A29
0 min. (-1=OFF)
A30
-10 °C / 0.0 bar
A32
1°C (0=OFF)
A44
0 min. (-1=OFF)
A45
0 min. (-1=OFF)
o03*
1
o04*
-
o05
1 (0=OFF)
o06
0
o12
50 Hz
o18
0
o20
-1 bar
o21
1 bar
o22
0
o23
0.0 h
o24
0.0 h
o25
0.0 h
o26
0.0 h
o30
0
20 min
2.0
20 K / 2.0 bar
4.0 / 0.3 bar
60 min
1.0
20 min
0.5
8
0
14
0
100%
0
ON
OFF
100°C / 60 bar
40.0 K / 10.0 bar 10.0 K / 3.0 bar
600 s
150
100%
0
ON
OFF
75%
20%
50%
10%
90 min.
0 min.
30°C / 40 bar
-40°C / 0.5 bar
999 min.
OFF
999 min.
OFF
999 min.
OFF
200°C/200.0 bar 60.0°C / 60.0 bar
140°C
OFF
999 min.
0 min.
999 min.
0 min.
990
-
100
OFF
7 (1)
0
60 H
0
18
0
0 bar
-1.0
200 bar
12.0
2
0
99.9 h
0.0
99.9 h
0.0
99.9 h
0.0
99.9 h
0.0
31
0
To be continued