Outdoor Unit Troubleshooting - Haier 1U12BS1ERA Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1.
1U07BS1ERA 1U09BS1ERA
1U12BS1ERA
1U18FS1ERA
1U24GS1ERA
2.
Connection of pipes
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
and the bending radius should be 30 to 40 mm or longer.
Connecting the pipe of gas side first makes working easier.
The connection pipe is specialized for R410A.
Half union
Spanner
Be careful that matters, such as wastes of sands,water, etc. shall not enter the pipe.
CAUTION
The standard pipe length is C m. If it is over D m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to E g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then
additional refrigerant.
Indoor unit
B
A
Outdoor unit
Outdoor unit
Oil trap
B
Indoor unit
A
Forced fastening without careful centering may
Flare nut
damage the threads and cause a leakage of gas.
Pipe Diameter(ǿ)
Liquid side6.35mm(1/4")
Liquid/Gas side9.52mm(3/8")
Gas side 12.7mm(1/2")
Torque wrench
Gas side 15.88mm(5/8")
Outdoor unit
B
Indoor unit
A
Amax
Max.Elevation:
In case the elevation A is more
than 5m, oil trap shoud be
installed every 5~7
Max. Length:
Bmax
In case the pipe length B is
more thanDm, the refrigerant
should be charged, according
to E g/m.
10
Fastening torque
18N.m
42 N.m
55N.m
60 N.m
charge

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

1u09bs1era1u07bs1era1u18fs1era1u24gs1era

Table des Matières