Technical Data; Safety Related Data - DOLD SX01A Traduction De La Notice Originale

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Technical Data

Mechanical Data
Mechanical principle:
Enclosure:
Internal parts:
Locking force:
Degree of protection:
Operating speed:
min. / max.:
Input
Nominal voltage U
N
(Rated voltage):
Nominal voltage range:
Power consumption:
Output
Contacts:
Switching element:
Switching principle:
Contact material:
Max. switching frequency:
Max. operating current:
Utilization category of
switching elements
to AC 15:
to DC 13:
Electrical service life:
Short circuit strength,
Max. fuse rating:
Conditional rated
short-circuit current:
(rated conditional short circuit
current):
Mechanical life:
General Data
Temperature range:
Storage temperature:
Rated impuls voltage:
Rated insulation voltage:
Overvoltage category:
Pollution degree:
Connection:
Cross sections
min. / max.:
Cable entry with thread:
Intended use:
Mounting:
Test principles:
Rotating axis with redundant actuation
Stainless steel V4A / AISI 316L
Stainless steel V4A / AISI 316
(acc. to EN 10027-2
1.4401; 1.4404; 1.4542;
1.4301; 1.4310)
F
4000 N
zh
IP 65
100 / 500 mm/s
AC/DC 24 V
0.85 ... 1.1 U
N
0.3 W
1 NC contact,
2 antivalent changeover contacts
IEC EN 60947-5-1 Appendix K
Changeover contact with forced opening
spring contact
Ag / AgSnO
2
360/h
2 A
1 A
0.5 A
5 x 10
switching cycles
6
2 A gG
1000 A
1 x 10
switching cycles
6
- 25°C to + 65°C
- 40°C to + 80°C
0.8 kV
≤ 50 V
III
2
Cage clamp terminals
0.25 / 0.75 mm²
(with ferrules and sleeve
according to DIN 46228-4)
1 x M20x1.5
Up to max. cat. 4, PL e according
DIN EN ISO 13849-1
According to DIN EN 50041
DIN EN ISO 13849-1:2015
DIN EN ISO 14119:2014-03
DIN EN 60947-5-1:2017
GS-ET-15:2015-05
GS-ET-19:2015-05
GS-ET-31:2010-02

Safety Related Data

Data suitable for the PFH
summation method according to
d
EN ISO13849-1: 2016
Data
according to
EN
ISO13849-1:
2016
Category
2
PL
d
PFH
3.18299E-09 2.05378E-09 1.63371E-09 2.00244E-10
D
T
20
10D
CCF
65 ...100
required
B
2 x 10
6
10d
d
(d/a)
365
op
h
(h/d)
24
op
t
(h)
1
cycle
n
8760
op
Diagnostics
Coverage
60 %
ratio DC
Test interval
1 / year
Category 2: The prerequisites for installation and integration into a
category 2 architecture must be met
Category 3: The prerequisites for installation and integration into a
category 3 architecture must be met
Category 4: The prerequisites for installation and integration into a
category 4 architecture must be met, in particular 2
actuators must be used
When used as a „stand-alone unit" (not as part of a key trans-
PFH
:
D
fer system), the safety parameters in the table above apply
When used as part of a key transfer system:
- PFH
total STS system = SUM PFH
D
- Lowest category of a module = category of whole
STS system
- Lowest DC of a module = DC entire STS unit
!
If the design of a unit is changed, the safety-related data may also
change.
22
SAFEMASTER STS-SX01A, SX01BM / 23.09.19 en / 135A
SX01A,
SX01BA,
SX01BM
SXBBM
3
3
d
e
20
20
85 ...100
85 ...100
85 ...100
2 x 10
6
2 x 10
6
2 x 10
365
365
24
24
1
1
8760
8760
60 %
90 %
1 / year
1 / month
1 / month
+ ... PFH
D1
4
e
20
6
365
24
1
8760
99 %
Dn

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sx01bmSafemaster sts rx11m

Table des Matières