SETTING MENU.

On this menu you have all adjustable parameters
of your installation.
Several parameters are not available with all systems.
In order to enter in the setting menu press on the same
time on the (-
) and (
installation menu (the first parameter "TkM1" is displa-
yed), you could choose another parameter by pressing
the navigation key (OK).
Once the desired parameter displayed you can change
the value with the keys (
4.1

MAXIMUM TEMPERATURE ON TANK 1.

"TkM1" parameter (Default value "65°C").
- Maximum value of desired water temperature on the
tank1 during normal operation. (Adjustable 15 to 95°C
with factory value 65°C).
4.2
MAXIMUM DELTA TEMPERATURE FOR
TANK 1
"dtM1" parameter (Default value "15°C").
- Difference between collector temperature T1 and tank1
temperature T2 to start the main pump1. (Adjustable
3 to 40°C with factory value 7°C).
4.3
MINIMUM DELTA TEMPERATURE FOR
TANK 1.
"dtm1" parameter (Default value "7°C").
- Difference between collector temperature T1 and tank1
temperature T2 to stop the main pump 1. (Adjustable
2 to (dTMax tank1 -2°C) with factory value 3°C).
4.4

MAXIMUM TEMPERATURE ON TANK 2.

"TkM2" parameter (Default value "65°C").
- Maximum value of desired water temperature on the
tank2 during normal operation. (Adjustable 15 to 95°C
with factory value 65°C).
+) keys. When you enter on the
+) or (-
).
4.5
MAXIMUM DELTA TEMPERATURE FOR
TANK 2.
"dtM2" parameter (Default value "15°C").
- Difference between collector temperature T1 and tank2
temperature T3 to start the main pump 1. (Adjustable
3 to 40°C with factory value 7°C).
4.6
MINIMUM DELTA TEMPERATURE FOR
TANK 2.
"dtm2" parameter (Default value "7°C").
- Difference between collector temperature T1 and tank
2 temperature T3 to stop the main pump 1. (Adjustable
2 to (dTMax tank 2 -2°C) with factory value 3°C).
N.B.: With a system with two tanks you could choose
a priority tank in the "Installation" menu in submenu
"Priority tank", and also choose the time of the loading
cycle for the secondary tank in submenus "Prio tank
load" and "Prio tank break".
4.7

TIME DELAY P2.

"P2dY" parameter (Default value "1 min").
Available only with the system 6.
- delay time for the start up of the pump P2 after the
pump P1 start up. (Adjustable 0 to 30 minutes with
factory value 1 minute).
4.8
MINIMUM TEMPERATURE ON
COLLECTOR.
"mtCo" parameter (Default value "25°C").
- This setting level is used to define a minimum tempe-
rature on the collector to authorize the solar loading.
(Adjustable between 0°C and 99°C with default value
25°C).
33