Balancing Reset; Checkout - Honeywell TrueFRESH ERV/HRV Série Guide D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Balancing Reset

NOTE: Once balancing is completed, balancing cannot be changed without resetting the unit.
To reset:
1. Press the (+) and (–) buttons simultaneously for 10 seconds.
2. Indicator light will turn yellow at 5 seconds.
3. Indicator light will turn green at 10 seconds.
4. Release both buttons.
5. Unit has been reset and can be put into balancing mode again.

Checkout

Apply power to the unit. Move the selector switch to the CONT position to verify that the unit turns on in
continuous speed.
Initiate a ventilation call from each of the external controls. Verify that the ERV/HRV unit turns on in high speed.
Return the selector switch to the desired position and the external controls to the desired settings.
Inspect the ducting to ensure that there are no kinks and correct as necessary.
Airfl ow Measurements - VNT5070 only
The VNT5070 ventilators are balanced by utilizing pressure ports located on the duct collars and a pressure-
airfl ow correlation table provided as a decal on the side of the unit.
NOTE: The VNT5150, VNT5200, VNT6150 & VNT6200 ventilators are not provided with pressure ports or
correlation charts. Instead, they are balanced by using air flow grids or pitot tubes which measure airflow
directly in each airstream.
Pressure-airfl ow correlation table:
32
Pressure Differential
Pa
in. W.C.
50
0.20
62
0.25
75
0.30
87
0.35
100
0.40
112
0.45
125
0.50
137
0.55
150
0.60
162
0.65
175
0.70
187
0.75
199
0.80
SELECTOR SWITCH
Fresh Air
L/s
CFM
44
93
41
87
39
83
37
79
35
74
33
69
30
65
29
61
26
56
24
50
22
46
19
41
17
36
TrueFRESH™ ERV/HRV Ventilation Systems 69-2480EF—13
LED
3-POSITION
SPEED CONTROL
BUTTONS (+ AND -)
Exhaust Air
L/s
CFM
43
90
40
85
37
79
36
77
36
76
34
71
32
67
28
60
24
51
22
47
19
41
17
36
15
31
Speed
Control
Open for
Instructions
M32371