INSTALLATION

Security warnings
The following instructions must be observed during installation and operation of
equipment:
 The equipment must be installed by authorised and qualified
personnel who comply with the instructions of this manual.
 The equipment must be installed and activated in compliance with
the current low voltage regulations.
 Do not use the equipment for purposes other than that specified.
 Before installing the smart charger, check that it is not damaged.
 Before accessing the connecting terminals, verify that the cables
are not under electric voltage. The opening of the enclosure does
not imply the absence of tension within it. It may only be opened by
authorised and qualified personnel.
 In accordance with the applicable regulations, the installer should
check whether overvoltage protection measures are necessary.
 Use only the specified charging cable for each electric vehicle. In
no case should another type of extension cable be used.
 In case of malfunction, do not perform repairs and contact our
Technical Services immediately.
 After installation, inaccessibility to connecting terminals without
appropriate tools should be ensured.
 Ensure appropriate tools are always used.
 To protect the intelligent charger against potential vehicle impacts,
the installation of a protective barrier is recommended.
Assembly requirements
 The minimum installation height of the power outlets and
connectors should be 0.6 m above ground level. If the charger is
intended for public use, the maximum height shall be 1.2 m and
in places for persons with reduced mobility, between 0.7 m and
1.2 m. (See the instructions of the country where the installation
is carried out in case other heights are specified).
 The mounting plate must be located at a height between 0.4 m
and 1.5 m above ground level.
 The charger must be installed upright and allow clearance for
maintenance.
 Use seals or presses to ensure the level of IP protection of the
charger.