EMKO ESM 20 Serie Manuel D'installation page 9

Masquer les pouces Voir aussi pour ESM 20 Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Easy Access Diagr am For Sensor Break Output Value
Main Screen
°C
°F
PO
AO AS
ASET
To enter the Sensor
Break Output Value,
press ASET/OK
button for 5 seconds.
°C
°F
PO
AO AS
PSET
P
Note:If user does not do anything for 120 seconds while device is on this section, device turns
to operation screen.
Note-2: Sensor Break Output Value can be adjusted on programming section too.
Tune Operation
Starting the Tune operation
1-Enter to the programming section
2- Select
,
,
parameter and turn to the main operation screen.
3- Observe that "
Note- For starting the Tune operation,
Heating Tune Operation:Process value must be lower than process set value at least 5% of
full scale
Cooling Tune Operation :Process value must be greater than process set value at least
5%of the full scale . If this condition is not okay, Blinks on the screen for 10 seconds.
Canceling Self Tune operation :
1- If sensor breaks ;
2- If Self Tune operation can not be completed in 8 hours ;
3- While heating Self Tune is running, if process value becomes greater than Process Set
value
4- While cooling Self Tune is running, if process value becomes less than Process Set value;
5- While Self Tune operation is running, if user changes the process set value;
Then Self Tune operation is canceled,
without changing PID parameters.
: Process Menu Parameters
: Process input type selection ; (Default:
: J type (Fe,Cu,Ni) Thermocouple ,
: K type (Ni,Cr,Ni) Thermocouple ,
: R type (Pt13%RhPt) Thermocouple ,
: S type (Pt10%RhPt) Thermocouple ,
: T type (Cu,Cu,Ni) Thermocouple ,
: Pt - 100 ,
-200°C,650°C ; -328°F,1202°F
: Pt - 100 ,
-199.9°C,650.0°C ; -199.9°F,999.9°F
: Unit Selection.
: Operation Scale minimum (Low
process input type and scale. (Default: -200)
:
Operation Scale
process input type and scale. (Default: 900)
°C
°F
PO
AO AS
Change the Sensor
Break Output Value
with increment and
decrement buttons.
Press ASET/OK button to exit and save.
ASET
parameter in
" blinks in set display.
device continues to run with former PID parameters
-200°C,900°C -328°F,1652°F
-200°C,1300°C ; -328°F,2372°F
0°C,1700°C ; 32°F,3092°F
-200°C,400°C ; -328°F,752°F
or
can be chosen. (Default:
Limit) value
maximum (High Limit) value.
°C
°F
PO
AO AS
PSET
P
Press PSET button to exit
without saving the value.
menu. Press ASET/OK button for saving the
)
;
0°C,1700°C ; 32°F,3092°F
)
. It changes according to the
It changes according to the
ASET
9

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Esm-4420Esm-7720Esm-9920Esm-9420Esm-4920Esm-20 serie

Table des Matières