4.2 Assembly instructions
The national installation regulations apply during the
assembly.
Provide shut-off fixture to ensure that cartridges can
be replaced.
1.
Thoroughly flush pipework
2.
Install refilling unit (VE300S) and mount using wall
bracket
• Install in horizontal pipeline
• Note flow direction (indicated by arrow)
• Install without tension or bending stresses
3.
Screw cartridge (see accessories) into refilling unit
(VE300S) and tighten by hand
5

Start-up

5.1 Measuring the water hardness
1.
Before installation, the total hardness measuring
instrument provided should be used to measure the
water hardness in order to set the electronics module
Observe the information in the instruction manual of
the total hardness test-kit
5.2 Pre-rinsing and bleeding cartridge
1.
Place bucket under system
2.
Open shut-off valve on inlet
3.
Open bleeder valve
4.
Drain out water via bleeder valve
• approx. 5 l with P300-S
• approx. 15 l with P300-L and P300-LES
5.
Close bleeder valve
6.
Check cartridge for leaks
5.3 Setting up the electronics module
1.
Take out electronics module
2.
Insert batteries
3.
Reattach electronics module
4.
Set electronics module, see Operation chapter
5.4 Filling up the system
1.
Slowly open shut-off valves on inlet and outlet
2.
Fill/refill heating system according to standard
3.
To rule out the possibility of uncontrolled refilling, after
filling the system, close the shut-off valves!
GB
6

Operation

6.1 Overview of display and control
keys
Display area
1
Service LED
2
Flashing yellow
flashing red + tone
3
Control keys
4
Selection fields
6.2 Control keys
Various menu items can be accessed from the control keys.
The menu items can be paged through by repeatedly
pressing the corresponding control key.
The active menu item is indicated by the selection fields in the
display.
The selection is confirmed by hovering over the active menu
item for more than 3 s.
ON/INFO
Remaining capacity Display of current remaining cartridge
capacity in litres
Consumption
Display of cartridge volume used to
date in litres
Total filter
Display of total volume to date in litres
Audio OFF
Switch off acoustic monitoring signal
Audio ON
Switch on acoustic monitoring signal
The factory setting is Audio ON
4
Plain text display for rinse, fill and
refilling quantities
cartridge capacity below 10 %
Cartridge capacity all used up
Cartridge in use for more than 5
years
Paging through the menu items
Display of active menu item
MU1H-1564GE23 R0420