Read the complete manual before carrying out the installation and activating the system.
1. DESCRIPTION
The dim controller enables all dimmable light atmospheres to be created via the Nikobus. These atmospheres
are saved in the memory and can be immediately called up by pressing a key without having to dim each lamp
again separately. You can easily set and modify the different light atmospheres yourself by means of the Nikobus
push buttons. The dim controller has 4 voltage controlled 0-10V outputs. Each of these outputs controls one or
more power dimmers. The power control is galvanically isolated in the connected dimmers. The 0V terminal is
bridged within the dim controller. At 0V, the connected lamp will be completely turned off. There is an analogue
control voltage over the entire 0-10V range. At 10V, the lamp is turned on for 100%. Any 0-10V compatible
dimmer with galvanically isolated control inputs can be connected to the Nikobus dim controller. One or more
dim controllers can be connected in parallel to the switching or shutter control units via the bus cable. Take into
account the polarity (B1—>B1, B2—>B2) of the bus connection. The dim controller has a diagnosis reporting
facility. As with the switching and shutter control units, the interchangeable EEPROM non-volatile memory
saves an identification number, the settings, the dimmer parameters for each output, the last set values and the
dimming settings in case of a power failure. Identification LEDs and a sound signal ensure a clear indication of
all functions during programming.
2. PARTICULARS
Start-up function:
Press the select-key briefly in order to select the outputs manually. Press long (>1s.) to temporarily switch on
the output:
• if the bus is not yet installed
• to control the outputs in case of a bus fault (short circuit or interruption)
• to test or localize output circuits.
Diagnosis reporting
During normal operation (not during programming) there is continuous diagnosis reporting on the 7-segment
display:
- a horizontal dash lights in case a correct Nikobus telegram is received
- a capital A blinks in case of short circuit or polarization errors (e.g. change in bus polarity between 2
modules)
- a small b blinks in case of bus power supply errors (circuit defect)
- a capital C blinks in case of a memory communication error (e.g. EEPROM defect) or in case a wrong module
type is used (e.g. shutter control module memory located in a dim controller).
Central functions with operating time (1 to 3s. in modes M5 and M6)
The operating time can be set between 1s. and 3s. One application may be for safety reasons: press a key for
2s. in order to switch off all lights. Another application: different actions are assigned to one key in function of
the operating time.
Definitions
Dmax: max. voltage at which no further visual change occurs
max. output voltage for a manual "on"-dimming function
Dmin: min. control voltage for a manual "off"-dimming function
Dstart: start/stop voltage when dimming on or off
voltage at which the lamp starts to glow
Example:
These parameters can be set individually for each output:
Dstart: between 0-2V in 16 steps (default value = 1.6V)
Dmin: between 1-4V in 16 steps (default value = 1.6V)
Dmax: between 6-10V in 16 steps (default value = 10V)
Settings T1 (rotary switch T1)
You can set 2 series of functions via the rotary switch T1:
- the first series determines which parameters are influenced by the settings T2.
- the second series determines the setting of specific control and delay times.
Times (rotary switch T1)
for modes M1, M2 and M3:
you can determine how the dim ON and dim OFF functions must react. The selected dimming speed T2 depends
on the position of rotary switch T1:
Setting rotary switch T1
dim ON
0
dimming speed T2
1
dimming speed 0 = 1s.
2-F
dimming speed T2
Control time for mode M5, M6:
0 = 0s., 1 = 1s., 2 = 2s., 3 = 3s., 4, ... = 0s.
Delay time for mode M7 (delayed OFF):
0 = 10s.
4 = 4min.
1 = 1min.
5 = 5min.
2 = 2min.
6 = 6min.
3 = 3min.
7 = 7min.
DIMMING SPEED rotary switch T2
"dimming time" OFF ->
Dimming speed:
Maximum:
rotary switch T2
(default values)
0
1s.
1
2s.
2
4s.
3
6s.
4
8s.
5
10s.
6
15s.
7
20s.
nv Niko sa Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel. +32 3 778 90 00 — fax +32 3 777 71 20 — e-mail: support@Niko.be — www.niko.be
dim OFF
dimming speed 0 = 1s.
selected dimming speed T2
selected dimming speed T2
8 = 8min.
A = 15min.
9 = 9min.
B = 30min.
C = 45min.
D = 60min.
"dimming time" OFF ->
Dimming speed:
Maximum:
rotary switch T2
(default values)
8
9
A
B
C
D
E
F
Mode
Function
Press the mode-key <1,6s. during programming in order to call up modes M1 to M8. The programming modes
are shown on the 7-segment display.
M1:
dim on/off
..............
M2:
dim on/off
..............
M3:
setting on/off
..............
M4:
setting on
..............
...............
M5:
on
..............
..............................
M6:
off
..............
..............................
M7:
delayed off
..............
M8:
blink
..............
.........................
Press the mode-key >1,6s. during programming in order to call up modes M11, M12, M13 and M14. The
programming modes blink on the 7-segment display.
M11:
preset on/of
............
M12:
preset on
............
................
M13:
dim on/off
............
M14:
dim on/off
............

3. TECHNICAL DATA

- Ambient temperature: 0 to 50°C
- Dim controller mains supply: 230V~ / 5W
2 terminals: max. 4 x 1,5mm
- Outputs: 4 x 0-10V, 2mA outputs
(not suitable for direct control of 1-10V "current sink" systems, such as electronic control gear - ECG). 1-10V
control according to EN60929 standard via interface ref. 65-330
max. 4 x 1,5mm
or 2 x 2,5mm
2
- Bus connection: 9V DC (SELV: safety extra low voltage)
2 terminals: max. 2 x 1,5mm
- Non-volatile EEPROM memory (4Kb)
- Dimensions: DIN housing 4 modules wide: H88 x W69 x D60mm

4. LEGAL PROVISIONS

- Connections must be made by a qualified person in accordance with the applicable regulations.
- This appliance is exclusively suitable for DIN-rail mounting. It must be mounted in a closed distribution
board.
- The appliance can only be connected to the mains after the necessary covers have been mounted into the
distribution board.
- This manual must be handed over to the user. It must be included in the electrical installation file and passed
on to any new owner. Additional copies are available via our website or our support service.
- During the installation, the following must be taken into account (not limited to list below):
dimming curve
- current legislation, standards and regulations;
- applicable technology at the time of installation;
- this manual, which must be read within the scope of each specific installation, only contains general
regulations;
- rules of proper workmanship.
- In case of doubt, you can consult Niko's support service or contact a registered control organisation.
Support Belgium:
+32 3 778 90 80
web-site : http://www.niko.be
E = 90min.
E-mail: support@niko.be
F = 120min.
In the event of defects, return your appliance, together with an extensive description of your complaint (type of
use, observed deviation...), to the registered Niko wholesaler.

5. GUARANTEE PROVISIONS

- Period of guarantee: 2 years from date of delivery. The delivery date is the invoice date of purchase of the
product by the consumer. If there is no invoice, the date of production applies.
- The consumer is obliged to inform Niko in writing about the defect, within two months after stating the
defect.
- In case of a failure to conform, the consumer has the right to a repair or replacement (decided by Niko) free
30s.
of charge.
40s.
- Niko cannot be held liable for a defect or damage as a result of an incorrect installation, improper or careless
50s.
use or wrong usage or transformation of the goods.
1min
- The compulsory regulations of the national legislation concerning the sales of consumer goods and the protection
2min
of the consumers in the countries where Niko sells, directly or via sister or daughter companies, chain stores,
3min
distributors, agents or permanent sales representatives, take priority over the rules and regulations mentioned
4min
above.
5min
Description
upper short: dimming on to last value
..............
.....................................................................................
upper long: dimming up to max. value
lower short: dimming off
lower long: dimming down to min. value
upper left: dimming on to last value
..............
.........................................................................................
lower left: dimming off
upper right, short: dimming on to last value
upper right, long: dimming up to max. value
lower right, short: dimming off
lower right, long: dimming down to min. value
upper left short: call up setting
........
...................................................................................................
lower left long: save setting
lower left: dimming off
upper right: dimming up
lower right: dimming down
short: call setting, long: save setting
........................................................................................
dimming on to last value, with adjustable speed
dimming off, with adjustable speed
.........................................................................................
dimming on to last value
............
...............................................................................................................
dimming down to min. value after certain time
on/off/on, ... with dimming speed 0
.........................................................................................
switch off with M6
upper left: call up preset
..........
...............................................................................................................
lower left: dimming off
upper right: dimming up
lower right: dimming down
call up preset
......................................................................................................................................
somple key mode
..............
.............................................................................................................................
short: switch between off and max. value
long: dimming up/down
with memory
..............
.......................................................................................................................................
short: switch between off and max. value
long: dimming up/down
or 2 x 2,5mm
per terminal
2
2
per terminal
2
per terminal
2
Support UK:
+44 1525877707
http://www.nikouk.com
sales@nikouk.com