Installation instructions, only for experts

4. Installation

4.1. Installing the control unit

ATTENTION!
Damage to the unit
The sauna control unit is protected against splashing water, however direct
contact with water could still damage the unit.
● Install the sauna control unit in a dry place at which a maximum humidity of
95% is not exceeded.
ATTENTION!
Sources of interference can have a negative effect on signal transmission
● Route all sensor leads separately from other mains cables and control leads.
● Use conduit to protect wires with only one layer of insulation (double insulation).
Observe the following points when installing the sauna control unit:
● The sauna control unit must be installed outside the sauna room or in accord-
ance with the recommendation issued by the sauna manufacturer.
● The ambient temperature must be within a range spanning -10 °C to +40 °C.
● The sensors may only be connected using the sensor leads supplied with the
unit, which are heat-resistant up to 150 °C.
The sensor leads may be extended under the following conditions:
● A silicon lead resistant to temperatures up to 150 °C is used.
● The minimum cross-sectional area of the wire is 0.5 mm
● The length of the heater sensor leads must NOT exceed 10 m.
Installing the sauna control unit
To install the sauna control unit, perform the following steps:
1. Screw two chipboard screws (3 x 25 mm) into the wall of the sauna at a height
of approx. 1.70 m and leaving a protruding length of 7 mm. The two screws
must be placed at a distance of 156 mm from each other (see Fig. 1).