USER INSTRUCTIONS.
- Before connecting the unit to electrical supply, ensure that the control button (5 contacts dial switch and thermostat) are at position 0.
- At the front of the unit (Figure ner 2) there is a 5 contacts dial switch knob, a thermostat knob and a manual reset button.
- When the dial switch knob is turned clockwise we will see the different possible manoeuvres. The fan works at any position of the dial switch knob
except 0. Turning the thermostat knob the heating elements are disconnected once the selected temperature is reached. The thermostat range is 0°C
to 40 °C. If the environmental temperature exceeds 40 °C, the ANB only will work in fan position.
- The 5 positions of the dial switch are as follows:
0
Stop
Fan
- The thermostat sets and maintains the desired temperature. Proceed as follows:
Once you have checked that mains voltage coincides with that indicated on the characteristics plate of the unit, insert the plug into the
electric supply.
Turn the thermostat to its maximum position.
Select the desired power.
When the desired temperature has been reached in the premises, slowly turn the thermostat anti-clockwise until a gentle «click» is heard
indicating that the heater battery has been disconnected. If the inside temperature of the air heater is higher than 44°C, the fan still works during
1 minute approximatetly. From this moment, the blower heater will come on and off automatically in order to maintain the selected temperature.
In order to switch off the unit, turn the knob to the stop position (0).
- When you stop the unit it is recommended to turn the dial switch knob to the fan position during approximately 5 minutes.
- To fix / change the angle of vertical orientation you must press the flange and put on one of the 5 possible positions of the air heater. With the air
heater placed, you must release the flange. You can see Figure ner 3 with the possible positions.
Figure ner2. Frontal diagram of the ANB.
Manual reset button of
the thermostat
4 Contacts dial
switch knob
ANB3,6SN
ANB3,6B
ANB6
ANB6SN
ANB9
ANB12
ANB17
5 Contacts dial
switch knob
SAFETY DEVICE AGAINST OVERHEATING.
The blower heaters incorporate a manual reset thermal protection that automatically disconnects the unit in cases of overheating.
When the safety thermostat disconnects the heating elements, the fan still works during 1 minute approximately . If this occurs, proceed as follows:
- Leave the unit to cool for approximately 15 minutes.
- Check the ANB installation is conforms to this instructions
- Check that there is not accummulated dirt on the grids, and if necessary clean them after disconnecting the unit from the mains
- Run again the air heater.In order to do so, press the manual reset button by using any object that can pass across the hole placed in the front part
of the air heater.
- If the problem persists, contact our Technical Department.
ORIENTABLE ELECTRICAL AIR
HEATER ANB MOBILE OR FIXED.
1/3 Heating power. Fan and thermostat are working. Excepting ANB3,6.
2/3 Heating power. Fan and thermostat are working.
Full heating power. Fan and thermostat are working.
Thermostat knob
Manual reset button of
the thermostat
ANB3,6
Thermostat knob
C/. Ca n'Alzamora, 34-36 - 08191 RUBÍ
Tels. +34 93 586 00 45
E-mail: electricfor@electricfor.com Internet: http://www.electricfor.com
NTC - 9804
Figure ner3.
Fixed positions of vertically orientation
Recommended operating angle for portable mode:
+20° / 0° / -18°
+20°
Recommended operating angle for fixed mode:
-18° a -54°depending on distance to floor.
-18°
Pag 10
Ed 17
26/06/06
-18°
-36°
-54°
Excepting ANB3,6