2
Fitting

*
"Normal
HC modules
I/O modules"
and additional
supply

I/O module 4/8 inputs (PNP/NPN)
or 4 outputs (only PNP 0.5 A)
or multi-I/O module 12I/8O
HC output (PNP/NPN)
*
High current supply (grey connection) ends
after last HC output module
PLEASE NOTE
A module for additional supply can:
– be fitted in any position to the left of the node;
– only be used by the high current output modules
(PNP or NPN, 2 A) which are fitted without
gaps to the left of the additional supply.
Several additional supplies are possible:
– maximum 12 electrical modules per terminal
(including additional supply).
10
!

*
HC modules
and additional
supply
!  
"Normal
I/O modules"
!
Additional supply
"
24 V/25 A
#
Node
Valves
"
#
9709 NH