CONNECTIONS
Any work on the module must be carried out by qualified maintenance personnel
who are fully acquainted with the specific hazards of electricity and able to take
the necessary precautions.
Non-authorized persons are absolutely prohibited from handling or working on the
module in operation.
This module generates high leakage current. The sub-assembly which receives the
module must be equipped with a warning label, near the mains connection.
The module connection is done through a powerblade connector including power and
signals pins.
The rectifier is directly connected to main power.
This class I (EN 60950-1) requires the grounding of the connector P4 (prominence pin on
system connector).
The rectifier may only be connected to TT, TN or IT circuit diagram.
The external protections must be of a size and rating to suit the application.
Internally no output terminal block is connected to the ground.
When in operation the positive polarity may be connected to the ground.
Connector characteristics
Inputs: 45A max by pin
Outputs: 45A max by pin
Signals: 1A max by pin
d3, b4, d5, b5, c5: Inputs 3Vdc max
a3: +5Vdc; 0.2 Amax
b3: 0Vs
d3: Factory reserved
b4: Can H
d5: Load sharing bus
b5: Can L
c5: SMbus
13/16
BN 13 3021/10/04