Sola HD CVS Hardwired Série Mode D'emploi page 8

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Table 11: Electrical Connections—Figure 6
Catalog Number
Primary Voltage
23-23-150-8
23-23-210-8
23-23-220-8
23-23-230-8
23-23-250-8
Secondary Voltage
Table 12: Product Parameters
Catalog Number
23-23-150-8
23-23-210-8
23-23-220-8
23-23-230-8
23-23-250-8
Table 13: Fusing & Wiring
Required Circuit Protection/Minimum Gauge for 90°C Wire
Catalog
Number
95–130
23-23-150-8
10 A/14 AWG
23-23-210-8
15 A/14 AWG
23-23-220-8
30 A/10 AWG
23-23-230-8
45 A/8 AWG
23-23-250-8
80 A/4 AWG
*Leads in the wiring compartment must have 105°C sleeving
8 | CVS HARDWIRED SERIES USER MAnUAL
Figure 6
Interconnect
H1 to H3 to H6 to H8
120
H2 to H5 to H7 to H10
H2 to H3 H7 to H8
208
H1 to H6 H4 to H9
H2 to H3 H7 to H8
240
H1 to H6 H5 to H10
H2 to H3 H5 to H6
480
H7 to H8
Interconnect
120
---
240
---
Input Voltage
175–235
190–260
6 A/14 AWG
6 A/14 AWG
10 A/14 AWG
10 A/14 AWG
20 A/12 AWG
15 A/14 AWG
25 A/10 AWG
25 A/10 AWG
40 A/8 AWG
40 A/8 AWG
X1 and X2 OR X3 and X2
VA
500
1000
2000
3000
5000
380–520
475–650
3 A/14 AWG
---
6 A/14 AWG
---
10 A/14 AWG
---
15 A/14 AWG
---
20 A/12 AWG
---
Connect Lines to
H1 and H2
H1 and H4
H1 and H5
H1 and H10
Connect Lines to
X1 and X3
BTU Output at Full load, +40°C Ambient
280
519
1229
1331
2117
Minimum Gauge for 90°C Wire
Output Voltage
120
208
14 AWG
14 AWG
10 AWG
14 AWG
8 AWG
12 AWG
8 AWG*
10 AWG
240

Publicité