Please read all safety, installation, and operating instructions before attempting to install or operate the unit.
Danger! High voltages are present inside the unit. Do not reach inside while it is energized. This unit contains no
!
user-serviceable parts.
Danger! Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. This signal
!
word is limited to the most extreme situations.
Warning! Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
!
Caution! Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury. It may also
!
be used to alert against unsafe practices.
The SolaHD Constant Voltage Sinusoidal (CVS) transformer provides voltage regulation and isolation from both transverse and
common mode noise for any type of load. It also suppresses transients with ferroresonant, protects overloads, and serves as a
dedicated line. It is the ultimate in ac power conditioning equipment.

4.1 receiving

Upon receipt, immediately inspect the unit for obvious signs of shipping damage and/or mishandling. If damaged, photograph the
unit, inform the carrier, and contact your SolaHD representative.
4.2 Mounting & Ventilation
These units are for use in an indoor humidity and temperature controlled environment. Mount the unit in either a horizontal or vertical
position. The unit should be located where contact with the transformer's hot surface is unlikely. If mounted in a vertical position (e.g.
on a wall), steel mounting hardware must be selected in accordance with Table 1. The wiring compartment should also be facing up.
Table 1: Mounting Hardware
CVS Rated VA
30–120 VA
250 VA
500–1000 VA
1500–10000 VA
15000 VA
All regulators generate a considerable amount of heat and depend on natural convection for adequate cooling. It is important
that ventilation openings not be obstructed. Mounting in a confined or poorly ventilated space should be avoided, unless special
provisions have been made for ventilation. For proper ventilation, allow a minimum of 12 inches of clearance above the unit and
minimum of 6 inches of clearance on each side.

1.0 Important Safety Instructions

2.0 Warnings Defined

3.0 Introduction

4.0 Installation Instructions

Steel Mounting Screws (Minimum Diameter)
#10 machine screws
1/4 in. bolts
5/16 in. bolts
3/8 in. bolts
1/2 in. bolts
CVS HARDWIRED SERIES USER MAnUAL | 3