LOCATION AND INSTALLATION/VENTILATION
INSTALLATION CLEARANCES 30" WITH ISLAND TRIM
1-1/2"
[3.8]
ELECTRICAL SUPPLY LOCATION
NOTES:
SHADED AREAS INDICATE WHERE COMBUSTIBLE MATERIALS ARE NOT ALLOWED.
APPLIANCE TOP MUST BE LEVEL OR HIGHER THAN THE ADJACENT COUNTERTOP SURFACES.
"G" IS GAS CONNECTION ZONE ON REAR WALL. MOUNT SHUT-OFF VALVE AS HIGH AS POSSIBLE IN THIS
ZONE FOR EASY ACCESS WHEN RANGE IS INSTALLED.
"E" IS ELECTRICAL SUPPLY ZONE.
"W" IS APPLIANCE OPENING.
NOTE: HANDLE END CAPS PROTRUDE 1/8" BEYOND EACH SIDE OF THE RANGE. ALLOWANCE MAY BE
NEEDED FOR ADJACENT DRAWERS OR CABINETRY.
"V" IS MIN. CLEARANCE TO REQUIRED VENTILATION HOOD.
COMBUSTIBLE
MATERIALS
V
W
RECOMMENDED
GAS SHUT-OFF
VALVE LOCATION
7"
[17.8]
18"
G
[45.7]
11"
[27.9]
E
4"
[10.2]
FRONT VIEW
12"
[30.5]
MIN. CLEARANCE
TO NEAREST
COMBUSTIBLE
SIDE SURFACE
1
8
DIMENSIONS IN
BRACKETS [ ] ARE
IN CM.
2-1/2"
FINISHED
[6.4]
FLOOR
W
RANGE MODEL
KRD304
30" [76.2]
©2021 Hestan Commercial Corporation
(CONTINUED)
COUNTERTOP
FULL OVERLAY
DRAWER FACE
" [3.2 mm]
FULL OVERLAY
CABINET DOOR FACE
V
(MIN)
30" [76.2]