Unit Installation - Hitachi RPI-0.4FSN5E Manuel D'installation Et De Fonctionnement

Table des Matières

Publicité

UNITS INSTALLATION
3 UNITS INSTALLATION
!
D A N G E R
Check to ensure that the accessories are packed with the indoor
unit.
Do not install the indoor units outdoors. If installed outdoors, an
electric hazard or electric leakage will occur.
Consider the air distribution from each indoor unit to the space
of the room, and select a suitable location so that uniform air
temperature in the room can be obtained. It is recommended that
the indoor units be installed 2.3 to 3 meters from the floor level. If
the unit is installed higher than 3 meters, it is also recommended
that a fan be utilised to obtain uniform air temperature in the
room.
Avoid obstacles which may hamper the air intake or the air
discharge flow.
Pay attention to the following points when the indoor units are
installed in a hospital or other places where there are electronic
waves from medical equipment, etc.
Do not install the indoor units where electromagnetic wave is
directly radiated to the electrical box, remote control cable or
remote control switch.
Install the indoor units and components as far as practical or at
least 3 meters from the electromagnetic wave radiator.
Prepare a steel box and install the remote control switch in it.
Prepare a steel conduit tube and wire the remote control cable in
it. Then connect the ground wire with the box and tube.
Install a noise filter when the power supply emits harmful noises.
This unit is exclusive non electrical heater type indoor unit. It is
prohibited to install a electrical heater in the field.
Mount suspension bolts using M10 (W3/8) as size, as shown
below:
Do not put any foreign material into the indoor unit and check to
ensure that none exist in the indoor unit before the installation
and test running. Otherwise a fire or failure, etc., may occur.

3.1 UNIT INSTALLATION

3.1.1 Installation
Install the indoor unit with a proper clearance around it paying careful attention of installation direction for the piping, wiring and
maintenance working space, as shown below.

Service Space
RPI-0.4FSN5E
7
PMML0385 rev.2 - 12/2018
!
C A U T I O N
Do not install the indoor units in a flammable environment to avoid a
fire or an explosion.
Check to ensure that the ceiling slab is strong enough. If not strong
enough, the indoor unit may fall down on you.
Do not install the indoor units, outdoor unit, remote control switch and
cable within approximately 3 meters of strong electromagnetic wave
radiators such as medical equipment.
Do not install the indoor units in a machinery shop or kitchen where
vapor from oil or mist flows to the indoor units. The oil will deposit on
the heat exchanger, thereby reducing the indoor unit performance,
and may deform. In the worst case, the oil damages the plastic parts
of the indoor unit.
To avoid any corrosive action to the heat exchangers, do not install
the indoor units in an acid or alkaline environment.
When lifting or moving the indoor unit, use appropriate slings to avoid
damage and be careful not to damage the insulation material on units
surface.
For Concrete
Slab 150~160mm
I-Beam
Steel
Suspension Bolts
(W3/8 or M10)
RPI-(0.6-1.5)FSN5E
Wooden Bar
(60mm to 90mm Square)
Concrete
Nuts
Wooden Beam
Sling Bolt
Anchor Bolt
(W3/8 or M10)
Square
washers
(mm)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Rpi-6.0fsn5e

Table des Matières