Parameter Configuration:

Parameter
Value
10
1
20
300
21
53
22
10
24
3
25
2
40
3
41
2
42
1
43
1
47
500

Conveyor Oven Time Monitor with Over-Heating Alarm

Description:
An oven monitor displaying the "tunnel" time in minutes and seconds. The tunnel time is defined
as the time it takes for the heated object on the conveyor to travel from point A to point B in the
application diagram below. A visual indicator should activate if the tunnel time rises above a
preset limit of 22 minutes and 30 seconds which could cause overheating of the processed
material. The indicator should automatically reset when the tunnel time returns to the normal
operating range. For ease of use, the display should be averaged over a period of 1 second.
Application Diagram:
A
B
Heat Source
Tunnel Oven
Page
Ite
m
18:40
TACHOMETER
Dart DM8000 Meter
Rate Mode Setting (GPM is a rate-based unit)
Display should indicate 3.00 GPM (300) when motor at Reference RPM, parameter 21
This is the RPM at which the Display Reference, parameter 20, should be displayed
Pulses per revolution of shaft encoder or pickup is 10 PPR
Display filtering / averaging set to 3 seconds
Decimal point position set to XX.XX on display
Alarm active when display value is below lower limit
Constant alarm output with manual reset required
No silencing, reset on any button press
Flash display when alarm is active
Lower limit setting for 5.00 GPM (500). Limits are entered without regard for decimal
point position
Connect to
Coupling
Dart PU-2E
or equivalent
Valu
Tach
ENTER
Notes
Dart 253G or other Motor Control
4
6
2
8
0
10
Non-Reduced
Shaft
Gear Motor
Drive Train Specs:
1250 RPM at non-reduced
motor shaft equates to
9 minutes and 15 seconds
of tunnel time
17
ON
OFF
Coupling to
Chain Drive