The pressure sensor ⁄ differential pressure sensor PREMASGARD
for pressure measurement in gaseous and liquid media. It converts the measurand into
standard signals of 0 -10 V. Process connection is 2 x G ⅛ " - 27 NPT internal thread.
®
PREMASGARD
SHD -692 differential pressure transmitters are applied in piping and
hydraulic systems, in mechanical and plant engineering as well as in building automation.
Not applicable for ammonia and Freon !

TECHNICAL DATA:

Power supply: ........................ 24 V AC (+15 % ⁄ - 10 %)
Measuring ranges: .................. see table
Output signal: ........................ 0 -10 V, 3-wire connection
Electrical connection: .............. 0.25 - 1.5 mm², DIN EN 175301- 803 - A
Pressure connection: ............... screw pipe connection for 6 mm pipe
Type of pressure: .................... differential pressure
Measuring principle: ................ ceramic measuring cell
Medium: ............................... liquid or gaseous
Temperature of medium: .......... - 15 ... + 80 °C
Mounting: .............................. installation arbitrary
Enclosure: ............................. stainless steel 1.4305
Connecting head: .................... angle plug connector DIN EN 175301- 803 - A
Medium contacting parts:......... INOX 1.4305, ceramics, sealing material EPDM
Response time: ...................... < 5 ms
Class: ................................... 0.5 %
Total error: ........................... < 1.3 %
Overload range: ...................... see table
System pressure: ................... max. 25 bar (P1 + P2)
Bursting pressure: .................. 1.5 x system pressure
Insulating resistance: .............. ≥ 100 MOhm, at 20 °C (500 V DC)
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 65 (according to EN 60 529)
Standards: ............................ CE conformity,
Type ⁄ WG1
SHD 692
S H D 6 9 2 - 9 0 0
S H D 6 9 2 - 9 0 7
S H D 6 9 2 - 912
S H D 6 9 2 - 916
S H D 6 9 2 - 918
SHD 692
18 - 33 V DC
(G ⅛ " - 27 NPT internal thread)
with receptacle mounted
electromagnetic compatibility
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC
Measuring Range
0 ...0.1 bar
0 ...0.5 bar
0 ...1 bar
0 ... 2.5 bar
0 ...4 bar
®
SHD- 692 is used
(Max. One-Side
Overload)
(0.6 bar )
(3 bar )
(5 bar )
(12 bar )
(12 bar )
Connecting diagram
1
24V AC / 18-33V DC
Output pressure 0-10V
2
3
GND
3
2
Output
Item No.
U - variant
0 -10 V
1301- 4121- 0500-000
0 -10 V
1301- 4121-0510- 000
0 -10 V
1301- 4121-0520-000
0 -10 V
1301- 4121- 0530-000
0 -10 V
1301- 4121- 0540-000
SHD 692