With the 4-20 mA function turned "On" and the refrigerant gas concentration climbing, the 4-20 mA signal will ramp up
corresponding to the concentration (0-300 ppm, for example). The display will show "FAn" and "ALr" and sound as outlined
above.
Default Configuration – Factory Settings
The default Power Up Test setting is ON
The default Display setting is ON
The default Buzzer setting is ON
The default Alarm Relay Setting is activation at 300 ppm
The default Alarm Relay Configuration setting is Normally Open
The default Fan Relay Setting is activation at 100 ppm
The default Fan Relay Delay setting is 3 minutes
The default Fan Relay Minimum Runtime setting is 0 minutes
The default Fan Relay Latching condition is OFF
The default Trouble Fan Setting condition is OFF
The default 4-20mA Output setting is ON
To change settings, remove the Philips screw on the front of the RD-6. Pull off the front cover of the unit.