3-WIRE & 2-WIRE CENTRIPRO 1Ø MOTOR WIRE
3-WIRE & 2-WIRE CENTRIPRO 1Ø MOTOR WIRE
SIZING CHART
SIZING CHART
Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop
Motor Rating
Volts
HP
kW
115
½
0.37
230
½
0.37
230
¾
0.55
230
1 0.75
230
1.1
Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop
Motor Rating
Volts
HP
kW
115
½
0.37 12.6
230
½
0.37
230
¾
0.55
230
1 0.75
230
1.1
230
2
1.5
230
3
2.2
230
5
3.7
Tables based on values from NEC, Tables 310.16 and 310.17 and NEC, Chapter 9, Table 8 Conductor Properties.
NOTE: Motors and control boxes are designed to operate on 230V systems. Systems with low line voltage,
between 200 – 207 volts require the next larger cable size than shown in the 230V charts. If using a
3-wire motor with control box on a low voltage application switch to a 208V start relay.
The 2-wire sizing chart above is only for use with PSC type, 2-wire motors.
Temperature Conversions: 20º C = 68º F, 30º C = 86º F, 60º C = 140º F, 75º C = 167º F, 90º C = 194º F
PUMPSAVER 235
PUMPSAVER 235
GND
L2
L1
FUSED DISCONNECT
OR CIRCUIT BREAKER
L1
CT1
L1
L2
CT
PRESSURE SWITCH
OR
OTHER CONTROL
SW
L1
L2
YEL BLK RED
DELUXE CONTROL BOX
14
Motor Lead Lengths - CentriPro 2-Wire Motors -
60º C & 75º C Insulation - AWG Copper Wire Size
SFA
14
12
10
9.5
115 183 293
4.7
466 742 1183 1874 2915 4648 7379 11733 14803 18688 23544
6.4
342 545 869 1376 2141 3413 5419 8617 10871 13724 17290
9.1
241 383 611
11.0 199 317 505
Motor Lead Lengths - CentriPro 3-Wire Motors (CSIR) -
60º C & 75º C Insulation - AWG Copper Wire Size
SFA
14
12
10
87
138 221
6.3
348 553 883 1398 2175 3467 5505 8753 11044 13942 17564
8.3
264 420 670 1061 1651 2632 4178 6644 8383 10582 13332
9.7
226 359 573
11.1 197 314 501
12.2 180 286 456
16.5 133 211 337
27
206
PUMP
CT2
L2 IN L2 OUT
PUMP
MOTOR
8
6
4
2
463
721 1150 1825 2902 3662 4623 5824
968 1506 2400 3811 6060 7646 9652 12160
801 1246 1986 3153 5013 6325 7985 10060
8
6
4
2
349
544
867 1376 2188 2761 3485 4391
908 1413 2252 3575 5685 7173 9055 11408
793 1234 1968 3124 4968 6268 7913 9969
722 1123 1790 2843 4520 5703 7199 9070
534
830 1324 2102 2648 4217 5323 6706
326
507
809 1284 1618 2042 2577 3253
PUMPSAVER 111 / 233
PUMPSAVER 111 / 233
GND
L1
L2
FUSED DISCONNECT
OR CIRCUIT BREAKER
L1
L2
PRESSURE
SWITCH
OR OTHER
CONTROL
GND
PRESSURE SWITCH MAY BE INSTALLED
AHEAD OF THE PUMPSAVER WHEN
RAPID CYCLE PROTECTION IS
NOT REQUIRED
1/0
2/0
3/0
4/0
1/0
2/0
3/0
4/0
PUMPSAVER
111 / 233
L1
L1
L2
L2
IN
OUT
IN
OUT
L1
L2
GND
L1
L2
GND
PRESSURE SWITCH
OR OTHER CONTROL
L2
GND
L1
TO MOTOR OR CONTROL BOX