Wieland SVM 4001K-A Mode D'emploi page 13

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 15
Installation instructions
SVM 4001K-A / 4001K-C
Standstill monitoring for 1- and 3-phases motor without sensor
system
General data
Terminals and connection
Single-core or finely stranded
Finely stranded with wire-end ferrule ac-
cording to DIN 46228
AWG
Maximum tightening torque
Stripping length
Year: 260 days
Day: 8 h
AC1:
non inductive load / 250 V AC
AC15:
electro magnetically load / 230 V AC
DC1:
non inductive load / 24 V DC
DC13:
electro magnetically load / 24 V DC
Assembly, Disassembly
Dimension Diagram
SVM 4001K-A DC 24 V
Doc. # BA000926 – 02/2017 (Rev. D)
(translation from original)
screw-type terminals
1 × 0,2 – 2,5 mm²
2 × 0,2 – 1,0 mm²
1 × 0,25 – 2,5 mm²
2 × 0,25 – 1,0 mm²
26 – 14
0,5 – 0,6 Nm (5 – 7 lbf-in)
7 mm
Switching voltage 24 V DC
Load
Switching current
Cycles
Assembly
1
Attach device to DIN rail.
2
Press the device carefully
onto the DIN rail (in direc-
tion of arrow) until it locks
into place.
SVM 4001K-A / 4001K-C
spring-type terminals
2 × 0,2 – 1,5 mm²
2 × 0,25 – 1,5 mm²
24 – 16
7 mm
Contact durability
DC1 DC13 Year
1 A
1 A
769
91
5
384
45
10
192
23
20
SVM 4001K-C DC 24 V
Disassembly
3
Push device down (in direction
of arrow).
4
Release device and remove it
from the DIN rail (see arrow).
EN 13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Svm 4001k-cR1.188.4020.0R1.188.4030.0

Table des Matières