General Alarm Sounder 24Vaux Output Connection; Evacuation External Input Connection - Detnov CCD-103 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Sounders delay
Just in the lower left part of the panel's circuit, there is a double strip of pins for
programming the delay of the sounders. You can programme the delay to be from 0 to
10 minutes, placing the jumper in the position corresponding to the desired time. It is
possible to make an advanced programming placing the jumper in the PROG position.

4.1.4- General alarm sounder 24Vaux output connection

The extinguishing panel have a 24V auxiliary output. The total current of the output is
500 mA and it is protected by a common fuse.
The 24Vdc output is intended to supply voltage to the external auxiliary elements that
need a power supply, we don't recommend you use this output to supply elements that
have consumption when on standby.

4.1.5- Evacuation External input connection

This input allows us to activate the sounders remotely, by means of a short circuit in
the contacts.
4.1.6- Voltage free ventilation relays output connection
The extinguishing panel has a ventilation relay. It is an output that acts when Zone 1
and 2 are in alarm.
15
GB