Bradford White Heat Pump Water Heater RE2H50, RE2H80
IMPORTANT SAFETY NOTICE
This information is intended for use by individuals
possessing adequate background of electrical,
electronic and mechanical experience. Any attempt to
repair a major appliance may result in personal injury
and property damage. The manufacturer or seller
cannot be responsible for the interpretation of this
information, nor can it assume any liability in connection
with its use. This quick reference guide is provided for
information purposes only and does not replace, modify
or change in any manner the Owner's Manual and
Installation Instructions.
DISCONNECT POWER BEFORE SERVICING
IMPORTANT- RECONNECT ALL GROUNDING
DEVICES
All parts of this appliance capable of conducting
electrical current are grounded. If grounding wires,
screws, straps, clips, nuts or washers used to complete
a path to ground are removed for service, they must
be returned to their original condition and properly
fastened.
Display
Displays the current
temperature or the number
of days for vacation mode.
To display setpoint if display
has gone blank, press any
Heat Pump
(Only)
Utilizes heat pump only.
Hybrid
Utilizes the heat pump and
electric heating elements.
Electric
(Only)
Utilizes electric elements
only. Stops the fan, the
heat pump and the flow of
Vacation
Use this mode for periods
away from home.
Mode
Press this button to toggle
through the various heating
modes. Press and hold to
switch between ºF and ºC.
button.
cool air.
CAUTION
Double wall heat exchanger, suitable for potable water
connection.
SPECIFICATIONS
Capacity................................................50/80 US gal
Tank Max Working Pressure ........................150 PSI
Water Temperature Set Point Range ..100F - 140F
Electrical ........................... 240/208VAC 60 Hz 1-PH
Circuit Breaker .............................................. 30 Amp
Upper Element Wattage ...........................4500/3380
Lower Element Wattage ...........................4000/3004
REFRIGERATION SYSTEM
Compressor .................................................... 500 W
Refrigerant Charge (R134a) ..................29.1/30.9 oz
(50Gal/80Gal)
Compressor LRA ........................................... 14.0A
Compressor RLA ........................................... 2.56A
Typical High Side Pressure (70°F amb) .... 210-280
PSIA
Typical Low Side Pressure (70°F amb) 55-65 PSIA
Arrow Pad
Use the up and down
arrows to manually change
the water temperature, or to
select days for Vacation Mode.
Enter
Press to confirm selections.
Filter
The red LED indicates that
the filter needs cleaning.
Press and hold to reset.
238-52395-00 02/18

Publicité

Table des Matières
loading

Sommaire des Matières pour Bradford White RE2H50

  • Page 1 Bradford White Heat Pump Water Heater RE2H50, RE2H80 CAUTION IMPORTANT SAFETY NOTICE Double wall heat exchanger, suitable for potable water This information is intended for use by individuals connection. possessing adequate background of electrical, electronic and mechanical experience. Any attempt to...
  • Page 2: Service Mode

    T5 Ambient Air SERVICE MODE Sensor The Service Mode can be accessed by pressing and holding the UP Arrow and Enter buttons simultaneously for 5 seconds. You will first T4 Compressor hear a single beep when pressing the buttons, then a two-tone sound Outlet Sensor indicating the action was successful.
  • Page 3 Fault Fault Counts Condition Check Code Before Code Displayed Displayed Control checks to ensure evaporator is free of frost. Continuously verifies Probable refrigerant leak. Find and Repair. that T3a sensor (evaporator inlet temperature) is greater than 20F after 30 Check T3a sensor mounting, wiring and resistance. FC** minutes of run time.
  • Page 4 Electronic Expansion Valve (EEV) This valve replaces the capillary tube typically used in refrigeration appliances. The EEV meters the flow of liquid refrigerant entering the evaporator at the rate that matches the TOP COVER amount of refrigerant being boiled off in the evaporator (gas). SHROUD AREA GRAY the valve also maintains the proper “superheat”...
  • Page 5: Remarque Importante Sur La Sécurité

    Bradford White Chauffe-eau à thermopompe RE2H50, RE2H80 MISE EN GARDE REMARQUE IMPORTANTE SUR LA SÉCURITÉ Échangeur de chaleur à double paroi, adapté pour le raccordement à l’eau potable. Cette information est dédié aux personnes possédant une expérience adéquate en électricité, électronique FICHE TECHNIQUE et mécanique.
  • Page 6 Code Compte d’er- Situation Vérifier les items suivants : reurs avant d’erreur l’affichage du code Le contrôle fait une vérification pour s’assurer que l’évaporateur ne comporte Fuite de réfrigérant possible. Trouvez et réparez la fuite. Montage, pas de givre. Vérification continuelle du capteur T3 (température d’entrée de câblage et résistance du capteur T3a.
  • Page 7: Mode Entretien

    MODE ENTRETIEN L’accès au mode d’entretien se fait en appuyant et en maintenant T5 Air ambiant simultanément la flèche vers le haut et le bouton Enter pendant 5 secondes. Vous entendrez un signal sonore simple (1 bip) lorsque T4 Sortie du vous appuyez sur les boutons puis un autre signal sonore double Compresseur (2 bips) vous indiquant la réussite de l’accès.
  • Page 8 Soupape de détente électronique (EEV) Cette soupape remplace le tube capillaire utilisé typiquement dans les appareils frigorifiques. La soupape de détente électronique mesure le débit de liquide frigorifique pénétrant dans l’évaporateur selon un rythme correspondant à la quantité de réfrigérant bouilli de l’évaporateur (gaz). Cette soupape maintient également une “surchauffe”...