Water Flow Setting - Hayward HeatRelax HPR06M Manuel D'instructions Et D'installation

Pompe à chaleur pour piscine
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 3
4. USER INTERFACE (continued)

4.5 Water flow setting

While the heat pump is running and the water inlet and outlet valves are open,
adjust the by-pass valve to obtain a difference of 2°C between the water
inflow and outflow temperature (see Functional Diagram Section 3.1).
You can check the setting by viewing the inflow and outflow temperatures
directly on the control panel by following the procedure below.
Inflow
temperature
HeatRelax
5 s
Then adjust the by-pass to obtain a difference of 2°C between the inflow and
the outflow.
Press
once to exit the menu.
Note: Opening the by-pass valve creates a weaker flow which results in an
increased ∆T.
Closing the by-pass valve creates a stronger flow which results in a
decreased ∆T.
Outflow
temperature
HeatRelax
10 s
HeatRelax
13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Heatrelax hpr09mHeatrelax hpr12mHeatrelax hpr19m

Table des Matières