(2) Unit Function Selection
Set the functions of each indoor unit from the remote controller, as required. The functions of each indoor unit can be selected only from the remote controller.
Set the functions by selecting the necessary items from Table 1 and Table 2. (Default settings are also shown below)
Table 1. Itemized functions of the entire refrigerant system (select unit number 00 to 15)
Function
Power failure
Not available
automatic recovery
Available
Indoor temperature
Unit operating average
detection
Set by unit's remote controller
Remote controller's internal sensor
LOSSNAY
Not Supported
connectivity
Supported (unit is not equipped with outdoor-air intake)
Supported (unit is equipped with outdoor-air intake)
Power voltage
240 V
220 V, 230 V
Table 2. Itemized functions of the indoor unit (select unit numbers 01 to 04 or AL)
Function
100 Hr
Filter sign
2500 Hr
No filter sign indicator
Fan operation
Operation (Last set fan speed)
during thermo off
Stop
in heating
Operation (Low speed)
operation
Fan operation
Operation (Last set fan speed)
during thermo off
in cooling
Stop
operation
Note:
When the indoor unit functions were changed using the function selection after installation is complete, always indicate the set contents by entering
mark in the appropriate check field of Table 1 and Table 2.
[Function selection flow]
First grasp the function selection flow. The following describes setting of "Power voltage" of Table 1 as an example.
(For the actual setting procedure, see [Setting procedure] 1 to 0.)
1 Check the function selection set contents.
2 Switch to the FUNCTION SELECTION mode.
(Press A and B simultaneously in the remote controller OFF state.)
3 Refrigerant address specification → 00 (Outdoor unit specification)
4 Unit address No. specification
(Buttons C and D operation)
5 Registration (Press button E.)
6 Mode No. Selection → 04 (Power voltage)
7 Setting No. selection → 2 (220 V, 230 V)
(Buttons F and G operation)
8 Register (Press button E.)
0 Ending function display (Press buttons A and B simultaneously.)
[Procedure] (Set only when change is necessary.)
1 Check the set contents of each mode. When the set contents of a mode were changed by function selection, the functions of that mode also change.
Check the set contents as described in steps 2 to 7 and change the setting based on the entries in the Table 1 and Table 2. (Refer default settings, when change the
setting)
2 Set the remote controller to Off.
Press and hold down the A [FILTER] and B [TEST] buttons at the same time
for two seconds or longer.
"FUNCTION SELECTION" blinks for a while, then the remote controller display
changes to the display shown below.
Refrigerant address display
* If the remote controller enters the OFF state after the "FUNCTION SELECTION" and room temperature displays "
probably abnormal. Make sure there are no noise sources near the transmission line.
Note:
If you make a mistake during operation, end function selection by step ? and repeat selection from step 2.
Settings
Settings
(Unnecessary for single refrigerant system.)
→ 00 (Indoor unit specification)
(Specified indoor unit →
Fan operation)
NO
End?
YES
Mode no.
Setting no.
Check
1
01
2
1
02
2
3
1
03
2
3
1
04
2
Mode no.
Setting no.
Check
1
07
2
3
3
25
2
1
1
27
2
YES
Change
NO
refrigerant
address and unit
address No.?
9
3 Set the outdoor unit refrigerant address No.
When the C [
CLOCK (
address No. decreases and increases between 00 and 15. Set it to the refriger-
ant address No. whose function you want to select.
(This step is unnecessary for single refrigerant system.)
Default settings
Remarks
Approx. 4-minute wait-period
after power is restored.
Default settings
Remarks
(PEA-400/500)
When selecting fan operation
"Stop", set setting no. of Mode
no. "02" in Table 1 to "3". Be sure
(PEA-200/250)
to place the remote controller
inside the room to be air-condi-
tioned so that it can monitor the
room temperature.
F
TEMP.
ON/OFF
MENU
ON/OFF
E
BACK
MONITOR/SET
DAY
PAR-21MAA
CLOCK
OPERATION
G
C
D
) and (
)] buttons are pressed, the refrigerant
" have flashes for two seconds, communication is
or other
I
A
FILTER
CHECK
TEST
B
CLEAR
H
15

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pea-rp250 gaPea-rp400 gaPea-rp500 ga

Table des Matières