Powering On the Rack

1. Turn off the power to the branch circuits.
2. Turn off both power sequencers.
3. Connect one end of each of the provided power cables to a branch circuit.
Inputs A0 and A1 should be on the same branch circuit and B0 and B1 should be on the same
branch circuit. For redundantly powered systems, do not connect any combination of A and
B to the same branch circuit.
4. Connect the other end of each power cable to the power input panel.
5. Turn on power to the rack by switching on the branch circuits.
6. Turn on the power sequencers.
Power On indicator lights on both power sequencers should light.
Power On indicator lights on both power strips should light.