Connections; Controls / Front View; Display And Controls - Wöhner OMUS 30Compact Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

6. Connections

Control cable terminal assignment
Ui
PE
Input
Input
Warnig
(95)
+ 24Vdc
L2
(L1+ L2+ L3)
Error
1
2
3
4
5
6
7
8
9
10
11
12
Ui
Input
Input
Ground
(96)
(97)
Ground
L1
L3
inputs
Error
Error
+ Warning

7. Controls / Front view

Display and controls:

Main LED L1
• Auto(matic) / Manual LEDs
• Current limits 16A, 20A, 25A
• Hand ON button L1
Main LED L3
• Auto(matic) / Manual LEDs
• Current limits 16A, 20A, 25A
• Hand ON button L3
select change enter
Esc / Reset button
28
Main circuit phase sequence
T3
T2
T1
6
4
2
L1
1
1
6
L2
3
L3
7
12
5
Ansicht von außen
External view
L1
Hand
ON
Auto
Hand
16A
20A
25A
L2
Hand
Main LED L2
ON
• Auto(matic) / Manual LEDs
Auto
Hand
• Current limits 16A, 20A, 25A
• Hand ON button L2
16A
20A
25A
L3
Hand
ON
Auto
Hand
16A
20A
25A
Parameter setting button
• Select, Change, Enter
Esc/Reset
Overview of display functions
Status
Main LED
Auto LED
No 24V operating voltage, variable
Off
Off
mains voltage
Normal operation
Green
Green
Standby (on by pressing ESC-Reset for
Off
Off
8s, back by pressing it again for 4s)
Manual mode (manual key not
Green
Off
pressed)
Manual mode (manual key switches
Green
Off
load on)
Parameter setting
Off
The selected function flashes green
Warning current limit 16A, 20A, 25A
Affected LEDs
One of two green
reached, hysteresis 2A
flash yellow
Warning overtemperature
All flash
Like normal operation
Device continues to operate
yellow
Warning mains phase failure, or fuse
Affected
One of two green
tripped, is detected independently by
phases yellow
the load
Load failure, current on activation
Affected
One of two green
below 2A (only detectable at
phases flash
actuation), tip: Manual mode if no
yellow
load
Warning – emergency mode if the
Flash yellow
Flash
hybrid technology fails multiple times.
green
*Can only be detected during
actuation and using 2A load current
Error – current limit 16A, 20A and 25A
Affected flash
One of two green
significantly exceeded 18A, 23A and
red
29A
Error overtemperature
All flash red
All off
Device shuts down all phases
Error current without actuation,
Affected flash
Green
device defective (relays welded, not if
red
fuse missing)
1.
2.
3.
5
5
11(96)
11(96)
Revision 0, stand 05.2016
Manual
Current
Warning
Error
LED
limits
signal
signal
connec-
Connec-
tion
tion
11 - 5
11 - 12
11 - 6
Off
Off
Off
On
1
3
Off
1 × green
Off
1
Off
4
All 3 flash
Off
On
2
Off
4
yellow
Green
1 × green
On
2
Off
4
Yellow
1 × green
On
2
Off
4
On
Off
2
4
1 × green
On
Off
2
4
flash
On
2
Off
4
1 × green
On
2
Off
4
flashing
Affected
On
Off
2
4
all off
Off
Flash
On
Off
2
4
1 × green
Flash
Off
On
1
3
1 × green
On
2
On
3
Red
Flash
On
On
2
3
1 × green
4.
11(96)
(97)12
(97)12
(95)6
(95)6
11(96)
English.
Load
Off
Switched
Off
Off
Switched
Off
Switched
Switched
Variable
Variable
Switched
Affected
off
All off
Variable
29