CAUTION
Risk of Electric Shock the Battery Circuit is not isolated from AC, hazardous Voltage may exist
between battery terminals and ground. Test before touching with bare hands.
CAUTION
A Battery can present a Risk of Electrical Shock and High Short Circuit Current. The Following
Precaution Should be Observed When Working on Batteries:
A. Remove watches, rings, or other metal objects.
B. Use tools with insulated handles.
C. Wear rubber gloves and boots.
D. Do not lay tools or metal parts on top of batteries.
E. Disconnect charging source prior to connecting or disconnecting battery terminals.

Storage Instruction

For extended storage through moderate climate(-15 to +30 °C / +5 to +86 °F), the batteries should
be charged for 12 hours every 6 months by plugging the UPS power cord into the wall receptacle.
Repeat this every 3 months under high temperature (+30 to +45 °C / +86 to +113 °F) environment.
14
®