Additional Refrigerant Charge - Mitsubishi Electric City Multi PURY-P72TNU-A-BS Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LO
HI
・Use a scale that can measure down to 0.1 kg (0.1 oz).
・Recommended vacuum gauge: ROBINAIR 14830A Thermistor Vacuum Gauge or Micron Gauge
・Do not use a gauge manifold to measure the vacuum pressure.
・Use a vacuum pump capable of attaining a vacuum of 65 Pa (abs) within five minutes of operation.

9-9. Additional refrigerant charge

Charge refrigerant in a liquid state.
- Charging refrigerant in the gaseous state will change the composition of the refrigerant and lead to a performance drop.
Do not use a charging cylinder when charging refrigerant.
- The use of a charging cylinder may change the composition of the refrigerant and lead to a performance drop.
The amount of refrigerant that is shown in the table below is factory-charged in the outdoor units. The amount necessary for extended piping is not
included and needs to be added on site.
Unit model
Factory-charged amount [kg (oz)]
P72
P96
P120
P144
P168
The amount of refrigerant that is shown in the table below is the maximum amount to be added on site.
Unit model
Maximum amount to be added [kg (oz)]
P72T/YNU
P96T/YNU
P120T/YNU
P144T/YNU
P168T/YNU
P192T/YSNU
P216T/YSNU
P240T/YSNU
P264T/YSNU
P288T/YSNU
P312T/YSNU
P336T/YSNU
WT09106X03
5.2 (184)
8.0 (283)
8.0 (283)
10.8 (381)
10.8 (381)
28.3 (999)
33.5 (1182)
39.5 (1394)
38.5 (1359)
39.5 (1394)
58 (2046)
74 (2611)
74 (2611)
71.2 (2512)
68.4 (2413)
68.4 (2413)
68.4 (2413)
GB-27
Gauge manifold
Low pressure knob
High pressure knob
Service valve
Low-pressure pipe
High-pressure pipe
Service port
Three-way joint
Valve (vacuum pump)
Valve (for charging refrigerant)
Refrigerant tank
Scale
Vacuum pump
To indoor unit
Outdoor unit
Unit model
Factory-charged amount [kg (oz)]
EP72
EP96
EP120
EP144
EP168
EP192
EP216
EP240
Unit model
Maximum amount to be added [kg (oz)]
EP72T/YNU
EP96T/YNU
EP120T/YNU
EP144T/YNU
EP168T/YNU
EP192T/YNU
EP192T/YSNU
EP216T/YNU
EP216T/YSNU
EP240T/YNU
EP240T/YSNU
EP264T/YSNU
EP288T/YSNU
EP312T/YSNU
EP336T/YSNU
EP384T/YSNU
EP432T/YSNU
5.2 (184)
8.0 (283)
8.0 (283)
10.8 (381)
10.8 (381)
11.8 (416)
11.8 (416)
11.8 (416)
28.3 (999)
33.5 (1182)
39.5 (1394)
38.5 (1359)
39.5 (1394)
38.5 (1359)
58 (2046)
38.5 (1359)
74 (2611)
38.5 (1359)
74 (2611)
71.2 (2512)
68.4 (2413)
68.4 (2413)
68.4 (2413)
66.4 (2343)
66.4 (2343)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

City multi pury-p96tnu-a-bsCity multi pury-p120tnu-a-bsCity multi pury-p144tnu-a-bsCity multi pury-p168tnu-a-bsCity multi pury-p192tsnu-a-bsCity multi pury-p216tsnu-a-bs ... Afficher tout

Table des Matières