Commissioning; Electrical Connections - Camille Bauer SINEAX A 210 Mode D'emploi

Indicateur puissance multifunction
Masquer les pouces Voir aussi pour SINEAX A 210:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Last interval; t-0
,
... Previous interval; t-1, -2, -3, -4
Overload, out of range indicator
System value
Δ
Delta voltage
Energy meter
High tariff
Low tariff
Interval 0 Interval 1 Interval 2 Interval 3 Interval 4
Current
time t
t-0
t-1
Zero value suppression
PF resp. cosϕ:
Currents:

Commissioning

The multi-functional power monitor is made operational by swit-
ching on the power supply. The following appears sequentially on
the display:
1. Segment tests: all the segments of the displays and all the LEDs
are lit for 2 s.
2. Version of the software: e.g. A 210
3. The 3 line voltages at switching on.
Loss of the power supply
All the values configured remain during a loss of the power
supply. On reconnecting the power supply, the last mode selected
is displayed.

Electrical connections

Safety Disconnects
The mains supply power to the instrument must be
installed downstream from a switched current limiting
device.
The circuit protection device should be 20 Amps or
less, and must be rated for the available voltage and
fault current; 5 Amp fuses are preferred.
WARNING
All mains supply power to the instrument must be
installed downstream from a switched current limiting
device.
The circuit protection device should be 20 Amps or
less, and must be rated for the available voltage and
fault current; 5 Amps are preferred.
The national provisions (e.g. in Germany VDE 0100
"Conditions concerning the erection of heavy current
facilities with rated voltages below 1000 V") have to
be observed in the installation and material selection
of electric lines!
When using external PT's or CT's refer to the
manufacturer's information for connections for vol-
tage and current monitoring.
t-2
t-3
t-4
Display ---, if Sx < 0.2% Snenn
Display 0, if Ix < 0.1% Inenn
1.04
The electrical connections are identical for the SINEAX A 210 and
A 220.
Measuring input, acc. to measuring mode
I1
I2
U1
U2
1
2
3
4
5
6
I1
U1
I1
I2
U2
I2
UL: 3~300V
5A 50/60Hz CAT III
IEC: 3~500/290V 5A 50/60Hz CAT III
Mat: 149783/1234567/001
SINEAX A210
Man: 10/02
210-121200
NLBxxxx
SO
1 2
LOCK
22 21
20
1 2 +
Jumper
Pulse / Limit
value outputs
Symbol
Meaning
Device may only be disposed of in a professional
manner!
Double insulation, device of protection class 2
CE conformity mark. The device fulfi lls the require-
ments of the applicable EC directives.
Products with this mark comply with both the
Canadian (CSA) and the American (UL) requirements
Caution! General hazard point. Read the operating
instructions.
General symbol: Input
General symbol: Output
General symbol: Power supply
Measurement category CAT III for current and vol-
CAT III
tage inputs
I3
U3
N
No. 1
7
8
9
11
I3
U3
I3
N
Camille Bauer AG
Switzerland
100-230V AC
85-125V DC
50-400Hz 3VA
14 15
Power supply
21

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sineax a 220

Table des Matières