Starting Up; Menu Structure; Examples - J.E. StorkAir WHR 950 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Low - Medium - High by means of SA 1-3 V
WHR
2
1
4
PE N
L
SA 1-3 V
230V 50Hz
8g.
Unievent check valve
M
N
L
Valve
L1
N
L2
L3
8h.
The WHR has a cable and a Perilex plug for the electrical connection. The
connection must comply with NEN 50110 and locally applicable regula-
tions. The unit is not suitable for connection to the three-phase mains.
Inspect the complete installation.

9. Starting up

9.1 Menu structure

The [MENU], [
], [
] and the [OK] keys can be used to select the following programs.
Set timer
Menu
Set time delay
Menu
Set ventilation
Menu
Set temperature
Menu
Display status
Menu
Display malfunction history
Menu
Reset
Menu
The menus P1 and P2 are freely accessible while the menus P3 to P7
require an "access code" (352).
PERILEX:
L1
N
WHR
L2
L3
2
1
4
PE N
L
SA 1-3 V
230V 50Hz
WHR
N
L1
L2
L3
P1
Menu not in use
P2
P3
P4
P5
P6
P7
Accessing the menus
Order
Key
Display
1
Menu
P1
2
P2
3
"1 - -"
4
"3 - -"
5
OK
"- 2 -"
6
"- 5 -"
7
OK
"- - 3"
8
"- - 2"
9
OK
P3
10
P4
11
P5
12
P6
13
P7
Press [MENU] twice to exit the program. If no more keys are pressed, the program
will stop after five minutes and the display will return to the ventilation position.
The exception to this rule is menu P3. A period of thirty minutes applies here.
9.2 Example
Set the central position of the intake fan to 40%.
Order
Key
Display
1
Menu
P1
2
P2
3
"1 - -"
4
"3 - -"
5
OK
"- 2 -"
6
"- 5 -"
7
OK
"- - 3."
8
"- - 2"
9
OK
P3
10
OK
P31
11
P35
12
OK
50
13
40
14
OK
P35
15
MENU
P3
16
MENU
1
9.3 Set parameters
P1 Timer: Menu not in use. P2 Time delays
No. Description
21 Switch-on delay high position 0
Low voltage input
22 Switch-off delay high position 0
Low voltage input
P3 Ventilation
No. Description
31 Exhaust fan low position
32 Exhaust fan medium position
33 Exhaust fan high position
34 Intake fan low position
35 Intake fan medium position
36 Intake fan high position
37 Current exhaust fan position
38 Current intake fan position
34
Description
Timer
Time delays
Access code required (352)
First numeral of access code
Second numeral of access code
Third numeral of access code
Ventilation
Temperatures
Status
Malfunction history
Reset
Description
Timer
Time delays
Access code required (352)
First numeral of access code
Second numeral of access code
Third numeral of access code
Ventilation
Ventilation procedure
Select P35
Current setting
Select 40
Saves value 40
Ventilation position
Min.
Max.
Default Unit
15
5
Minutes
120
30
Minutes
Min.
Max.
Default Unit
15
98
30
%
16
99
50
%
17
100
90
%
15
98
30
%
16
99
50
%
17
100
90
%
Current value
%
Current value
%