.8.3 Technical data
Weight
Model
(lb)
(Kg)
172
78
200
Electrical
supply inlet
Model
200
230/1/60
Calibration values
200
MIN.- MAX
Ambient Temperature
Refrigerant
Amb
R407c (Kg)
During transport
and stockage
(oz)
(Kg)
32-122° F
45,8
1,3
0-50°C
Compressor
1
M1
RLA
LRA
(A)
(A)
7,5
24
Hot gas valve
9-HGV
66.7 - 69.6 PSIg
4.6 - 4.8 barg
Compressed
air inlet
Temperature
Aft er
installation
In
41-122°F
41 - 149°F
5-50°C
5 - 65°C
Fan motor
3
EV1
RLA
LRA
(A)
(A)
0,6
0,14
Fan pressure Switch
12-PV
ON: 261 PSIg
OFF: 203 PSIg
ON: 18 bar
OFF: 14 bar
Connections
Air - Side
Max
Working
Compressed
Pressure
Condensate drain
air inlet/outlet
203 PSIg
1.1/2" NPT - F
1/2" NPT - F
14bar
Maximum
Minimum
protection device
circuit ampacity
rating
MCA
HACR
(A)
(A)
7,8
High pressure switch
15-HP1
406 PSIg
28 barg
22
200
Sound
pressure level
[dB (A)]
55
Minimum section
validated cable for
electrical connections
Ø
10
14AWG
High temperature thermostat
16-ST
248°F
120°C