Télécharger Imprimer la page

Technical Data - Baumer PA210 Guide Utilisateur

Publicité

Les langues disponibles

Les langues disponibles

PA210
18

5 Technical data

Technical data - electrical ratings
Voltage supply
Display
Number of digits
Digit height
Display range
Display refresh
A/D transformer
Analog input
Programmable
parameters
Data memory
Standard
DIN EN 61010-1
Emitted interference
Interference immunity
Technical data - mechanical design
Ambient temperature
Storing temperature
Relative humidity
Connection
Core cross-section
Protection DIN EN 60529
Operation / keypad
Housing type
Dimensions W x H x L
Mounting
Material
Weight approx.
www.baumer.com
Supplied by active current loop -
voltage drop <5 VDC
LED, 7-segment display (with 60 unit
stickers for front)
4-digits
10 mm
-1999...9999 („OuE" to signal
overflow)
500 ms
Principle ∑∆
Resolution 16 bit
Measuring rate 62/s
Measuring accuracy ±(0.1 % +3 digit)
Temp. coeffic. 100 ppm/°C
Current input
Display range can be linearised
Decimal point
>10 Jahre in EEPROM
Protection class II
Overvoltage category II
Pollution degree 2
DIN EN 61000-6-3
DIN EN 61000-6-2
-10...+60 °C
-25...+85 °C
95 % non-condensing
Spring-loaded terminal connector,
detachable
1 mm² (grid 2.54)
2.5 mm
(grid 7 .62)
2
IP 65 (face)
3 softkeys below bezel
Built-in housing
48 x 24 x 68 mm
Front panel installation by clip frame
Housing: Polycarbonate, UL94V-0
50 g

Publicité