Télécharger Imprimer la page

LEGRAND Wattstopper ELCU-200-347 Instructions D'installation page 2

Dispositif de commande d'éclairage d'urgence

Publicité

Les langues disponibles

Les langues disponibles

Wiring Notes
1. You can connect as many NC contacts (including EMTS-100) in series on the jumper loop wire as you want to a single ELCU. You
cannot connect the NC devices in any other manner.
2. At no time can more than 5 ELCU devices can be controlled together by commoning their Test Loop wires to a Normally Closed
Test Switch (EMTS-100) and/or other NC contact closure.
3. If connecting ELCUs together via their test loop wires, you must maintain the polarity of their wires.
• ELCU units should be installed in accordance with state, local and national electrical codes and requirements.
• ELCU units are designed to attach to a junction box or electrical enclosures that are fitted with a 7/8" diameter opening (standard
1/2"knockout).
• ELCU units operate with power provided by two sources. Place a warning label on each enclosure that contains an ELCU unit.
Installation Procedure
1. Remove the locking nut from the ELCU unit and insert the unit's threaded nipple through the appropriate knockout. Tighten the
locking nut so that the unit is secured to the j-box or enclosure.
2. Connect the ELCU to the emergency lighting for the area controlled. Connect the Emergency wiring leads on the ELCU in series
with the emergency lighting load as shown in the wiring diagram. Connect the neutral for the emergency circuit to the Emergency
Neutral lead as shown in the wiring diagram.
Standard wiring for switch control of emergency lighting along with normal lighting
Alternate Remote Test/Firefighter Control
Normal Line
Normal Neutral
Emergency Power In
(Black 14)
Emergency Neutral
(Gray 18)
Emergency Line
"Always On"
Emergency Neutral
Alternate wiring for dimmer bypass on an emergency circuit
Alternate Remote Test/Firefighter Control
Normal Line
Normal Neutral
Emergency Power In
(Black 14)
Emergency Neutral
(Gray 18)
Emergency Line
Dimmer
"Always On"
Emergency Neutral
WIRING
Control
Device
Normal
Power Sense
(Black 18)
Emergency Power Out
(Red 14)
ELCU-200-347
Emergency Lighting Control Unit
120/277/347VAC 50/60HZ
16 A @120-347 VAC Ballast/CFL
/ELV/MLV/LED
16 A @120-277 VAC E-Ballast/CFL
CAUTION
See instruction manual for
installation, operation and
maintenance instructions
www.legrand.com/wattstopper • 800.879.8585
23033x1
Dimmer
Normal
Power Sense
(Black 18)
Emergency Power Out
(Red 14)
ELCU-200-347
Emergency Lighting Control Unit
120/277/347VAC 50/60HZ
16 A @120-347 VAC Ballast/CFL
/ELV/MLV/LED
16 A @120-277 VAC E-Ballast/CFL
CAUTION
See instruction manual for
installation, operation and
maintenance instructions
www.legrand.com/wattstopper • 800.879.8585
23033x1
INSTALLATION
2
Normal
Lighting
Normal
Neutral
Normal
(White 18)
Switch Sense
(Red 18)
Cut Jumper Loop
to use with
normally closed
- Test switch
- Fire alarm panel
- Security panel
- Other
Emergency
Lighting
Normal
Lighting
Normal
Neutral
Normal
(White 18)
Switch Sense
(Red 18)
Cut Jumper Loop
to use with
normally closed
- Test switch
- Fire alarm panel
- Security panel
- Other
Emergency
Lighting

Publicité

loading