DSC WS8916 Série Notice D'installation Et D'utilisation page 2

Publicité

Les langues disponibles

Les langues disponibles

Fi
2. Mount Smoke Detector Backplate
Secure backplate to the
mounting surface using the
screws provided.
CAUTION:
The
dust
cover protects the unit
when not in service.
Remove the dust cover
before use.
3. Install Batteries
If batteries are not
installed,
install
batteries
in
the
sequence
indicated.
Use
only
approved
Panasonic
CR123A,
Sanyo
CR123A
or
Duracell
DL123A
batteries. If batteries
are installed, remove
the
'Pull'
tab
to
activate.
4. Mounting
• Detector
Installation:
Position the detector on
to the base plate using
the detector and base
plate alignment marks.
Press the detector gently
in place while rotating
the detector clockwise
until the detector snaps
into place. Remove the
side tab from the locking
tab to lock in place
(optional).
• Removal: Depress tab
with
a
small
slotted
screwdriver. Rotate detector counter-clockwise until the alignment
marks line up. Remove detector.
1
Figure 3a
Locking
Tab
Mounting Holes
3V CR123A
Insert
Last
Mounting
Surface
Alignment
Marks
Detector
CLOSE
OPEN
Installer Compensation Reset
Cleaning or replacement of the smoke sensor chamber changes the
background signal/noise of the detector; this requires the drift
compensation be reset. Compensation trouble is one of the faults
indicated when the LED indicator is off while the siren is chirping.
1. Remove batteries, then short the detector battery contacts for 5
seconds to power down unit.
2. Replace batteries to power up unit while pressing the test button.
3. The tamper switch must not be pressed.
4. The LED will flash when 5 seconds has elapsed. Release the test
button within 2 seconds of the LED flash.
5. The LED will flash every 2 seconds for 1 minute. During this
period, the detector must be mounted.
Allow an additional 2 minutes for the detector to make
background level checks.
6. Test the detector to verify normal operation.
5. Test Unit
NOTE: The central monitoring station (if used) should be notified
3V CR123A
prior to the test being generated. This will prevent a false alarm and
an unnecessary response from the central monitoring station.
Insert
Initiate test by pressing the test button for 5 seconds minimum. Alarm
First
activation is indicated by the flashing LED, the siren, and transmission
of the alarm signal to the control panel. The detector restores to
normal when the test button is released.
NOTE: Allow a minimum of 20 seconds after power up and , after
test, alarm or tamper restore activations. Do not use test button
when smoke is present.
NOTE: If the detector is in one of the following states when a test is
initiated; it will not enter an alarm state.
• Tamper, (detector not installed on mounting plate)
• Compensation Trouble
• Other internal faults that could prevent a smoke or heat alarm.
PULL
DOWN
NOTE: Smoke sensitivity of installed detectors can be measured
Tab
without removal or an alarm being generated using the FSD-100
Smoke Detector Test Meter.
To test the unit using the FSD-100, set the test meter up to read
devices as per the instructions supplied. Depress the test button on the
smoke detector for 1 second and release.
NOTE: If the test button is held for 5 seconds or longer, an alarm
will be generated.
Backplate
Tabs
Move the test meter over the center of the detector, wait until you
hear the test meter beep, remove the unit and the information can be
immediately reviewed. Please see the instructions supplied with the
FSD-100 Smoke Detector Test Meter for more information.
6. Device Enrollment
The 6 digit serial number located on the back of the smoke detector
housing must be enrolled into the alarm control panel with Installer
programming. Refer to the receiver Installation Manual for details.
For placement tests remove detector from backplate for one second
(tamper) then reattach. Wait at least 30 seconds for test result before
activating again.
Fi
3