REMOVAL OF COVER
REFITTING COVER
■ 5.3. Leak checking and periodical inspections
A leak detection check must be carried out annually or as
specified by local regulations.
Use the appropriate equipment to empty or refill the cooling
installation (recovery machine, goggles, gloves, etc.)
■ 5.4. Electrical checks
Systematically check the tightening of all screwed electrical
components.
Check regularly:
- Safety and control devices,
- The condition of electrical and refrigeration connections
(e.g. for any loosening or oxidation),
- Operating conditions,
- The mounting of the condensing unit on its base,
- The housing fixings (no vibration),
- Crankcase heater operation.
■ 5.5. Filter drier
Silensys® condensing units are all fitted with a brazed filter
drier.
Replacement filter drier selection:
When changing the filter drier, ensure that it is replaced with
an equivalent in capacity and pressure drop and with the
correct direction of flow.
12/46
366430 / 05.2015_d
Installation Instructions |

6- WARRANTY

For information concerning the condensing unit warranty,
please refer to our sales terms and conditions.

7- DECLARATION OF CONFORMITY

- We hereby declare that Silensys® condensing units comply
with the Low Voltage Directive 2006/95/CE.
- The applicable standards are:
- CEI 60335-I [EN 60 335-I ]: Safety of electrical domestic
equipment and similar – General description
- CEI 335-2-34 [EN 60 335-2-34]: Safety of electrical domestic
equipment and similar – Specific regulations for motor
compressors.
- CEI 60335-2-40 [EN 60 335-2-40 ]: Electrical and similar
and similar household appliances safety – Specific rules for
electric heat pumps, air-conditioners and dehumidifiers.
- When incorporating our products into a machine, the
Declaration of Incorporation of the manufacturer must be
observed. Our condensing units are not required to comply
with Pressure Equipment Directive 97/23/CE as they are
classified as a compatible sub-assembly.
- Certificates of conformity are available on our website www.
tecumseh.com and on request.

8- DECLARATION OF INCORPORATION

Only qualified staff are authorized to work on the condensing
unit. This product is defined as for installation in machines
according to European Directive 2006/42/CE. .
It is not permitted to run the condensing unit before the
machine into which it is incorporated has been declared in
conformance with the pertaining legislation. The condensing
unit itself is therefore not required to comply with Directive
2006/42/CE.
In its constant endeavor to improve its products, TECUMSEH
EUROPE
S.A. reserves the right to change any information in this
instruction manual without prior notification.
Silensys® and L'Unite Hermétique® are registered trademarks
of TECUMSEH EUROPE S.A

Publicité

Table des Matières
loading

Table des Matières