Installation Location; Example For An Apartment - Gira 2330 02 Notice D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 44
2

Installation location

2.1

Example for an apartment

Smoke detectors should ideally be installed in front of or inside
bedrooms, so that the occupants will be woken up if there is a fire at
night. For optimum performance, install the smoke alarm device in the
middle of the room under the ceiling. If this is not possible, observe a
minimum distance of 50 cm to the walls.
The smoke detector can monitor rooms with a floor area up to a
maximum of 60 m
unfavourable conditions for smoke alarm devices, such as kitchens
(vapour from cooking), bathrooms (condensation), garages or very dusty
areas, smoke detection can be disabled in order to avoid false alarms
(Section 3.2). In this case, only the thermal function will remain active.
26
and a maximum height of 4.5 m. In rooms with
2
Minimum protection: one
smoke alarm device in the corridor
or stairwell.
Optimum protection: one
smoke alarm device in each
bedroom and living room.