Télécharger Imprimer la page

Etherma UT 40 Instructions D'installation Et D'utilisation page 7

Publicité

Les langues disponibles

Les langues disponibles

S P E C I F I C A T I O N S E T H E R M A U T 4 0
ETHERMA UT 40, 230 V, IP 65
Type
Art.No.
ET-UT-40
40555
S P E C I F I C A T I O N S
> Supply voltage
> Supply frequency
> Power switching capacity
> Load current
> Temperature range
> Temperature accuracy
> Current consumption
> Soft start duration
> Output & load fault detection
> Power & status LED indicators
> Supply terminal connections 0.2 to 6 mm² rising clamp
> Gland cable entry
> Ambient operating
temperature
> Ingress protection rating
> Built in Sensor
> Sensor monitoring
> Sensor terminal connections 0.1 to 1.5 mm² Rising
clamp
> Sensor mounting
> Enclosure dimensions
> Fixing hole & centre's
T E R M S O F G U A R A N T E E
Dear customer!
Please note our general terms and conditions. In the case of warranty cases, the country-specific legal claims apply, which you
must assert directly against your dealer.
WARNING: Electrical and electronic appliances often contain prescious materials. But they can also contain
harmful substances that were necessary for their function and safety. They can harm the environment if dis-
posed or mishandled. Please help to protect our environment! Therefore do not dispose of this device in the
residual waste. Dispose of this unit in accordance with local regulations. Dispose of the packaging materials,
replacement parts or equipment parts properly.
WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES. CHANGES, ERRORS AND MISPRINTS DO NOT CONSTITUTE A CLAIM FOR DAMAGES.
E T H E R M A U T 4 0
Electronic terhmostat for frost protection of pipes, IP 65, 0 to +40 °C, incl. 4 m sensor
230 V AC +/- 10 %
50 Hz
4 kW Max.
20 A Max.
0 °C to +40 °C
1 °C
15 mA
1 second
8 mm Ø (cable MUST be
round to ensure IP rating)
-20 °C to +40 °C
IP 65
Encapsulated 10 k ohm
NTC thermistor probe, 4 m
open or short circuit - unit
shuts down and alarms
To secure to pipe etc., use
appropriately sized nylon
cable ties
95 x 130 x 55 mm
4 x 4.8 mm Ø holes on
fixing centres 97 x 82 mm