condition may still be active.
3. The 'MINI-USB' outlet has two functions:
To connect the logger to the mains by means of the supplied USB
mains adaptor;
To download the measurement data via a separate USB/mini-USB
data cable (see Chapter 14, Accessories) (see Chapter 9, Read-
out).
4. A corrosion-alarm indicates that the corrosion rate at that time
has exceeded the pre-set threshold value. The damage caused to
the installation thereby depends on the value of the corrosion rate,
the frequency and/or the duration of the alarm. In an ideal situation,
the BMS should be programmed so that these conditions, possibly
combined with alarms from other Risycors in the same system, can be
sensibly passed on.
It is recommended to locate the cause of the problem and to correct
it if one of the following conditions is met:
- there have been more than 7 alarms in 7 weeks
- the alarm lasts longer than 7 days
- several Risycors in the same system give alarms at the same
time
Contact your installer / technician.