Specifications - GMC-I PRO SyS ACF 3000_4/24 Notice D'utilisation

Sondes de courant ca flexible
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. SPECIFICATIONS

Electrical characteristics
Current range
Calibrated output V
RMS
Accuracy (at 25°C, 50 Hz)
Interchangeability variance
Linearity (10% to 100% of range)
Internal Resistance
Minimum load resistance
Bandwidth (-3dB)
Phase Error (45 - 65Hz)
Temperature coefficient
Position sensitivity
External field (with cable >100mm from the head)
Working voltage
Probe
Probe and cable material
Probe cable length / maximum conductor diameter
Probe cable diameter
Output cable length (P-01.713.9 / P-01.714.4)
General Characteristics
Operating temperature range
Storage temperature range
Operating humidity
Degree of Protection
Safety
Safety standards EN 61010-1:2001
EN 61010-031:2002
EN 61010-2-032:2002
EMC
EN 61326-2-2:2006
1000 V
, Category III; 600 V
RMS
ROHS and WEEE compliant
Rated for continuous use
Output Connections
Function
Colour
Output +
Red
Output -
Black
Screen
Green
at 1000 A
/ 50Hz
RMS
, Category IV; Pollution Degree 2
RMS
3000A AC
85mV
± 0.5% of reading
± 0.5% of reading
± 0.2% of reading
157 Ω ± 15 Ω
10kΩ
10Hz to 20kHz
± 1°
± 0.05% of reading / °C
± 2% of reading
± 0.25% of range
1000V AC
RMS
30V max (Output)
Alcryn 2070 NC, LATENE 7H2W V0
610mm (24"), 194mm (7.6")
9.9mm (0.39 inches)
2m / 5m, terminated with 8mm un-
insulated ferrules
-20°C to 65°C
-40°C to 75°C
15% to 85% (non condensing)
IP65
4
or DC (Probe)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

P-01.713.9Acf 3000_31/24P-01.714.4

Table des Matières