5 Maintenance and service
Tips about DHW tank temperature
Make sure the number (available hot water for x persons) on the
DHW tank temperature home page is NOT higher than your
actual needs.
Use a weekly schedule for your normal domestic hot water
needs (only in scheduled mode).
Program to heat up the DHW tank to a preset value
(Storage comfort = higher DHW tank temperature) during
the night, because then space heating demand is lower and
electric tariffs may be lower.
If heating up the DHW tank once at night is not sufficient,
program to additionally heat up the DHW tank to a preset
value (Storage eco = lower DHW tank temperature) during
the day.
Make sure the desired DHW tank temperature is NOT too high.
Example: After installation, lower the DHW tank temperature
daily by 1°C and check if you still have enough hot water.
Program to turn ON the domestic hot water pump only during
periods of the day when instant hot water is necessary.
Example: In the morning and evening.
5
Maintenance and service
5.1

Overview: Maintenance and service

The installer has to perform a yearly maintenance. You can find the
contact/helpdesk number via the user interface.
As end user, you have to:
Keep the user interface clean with a soft damp cloth. Do NOT
use any detergents.
Regularly check if the water pressure indicated on the
manometer is above 1 bar.
Refrigerant
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do NOT vent gases into the atmosphere.
Refrigerant type: R410A
Global warming potential value: 1975
Periodical inspections for refrigerant leaks may be required
depending on the applicable legislation. Please contact your installer
for more information.
5.2
To find the contact/helpdesk number
Go to [6.3.2]:
> Information > Error handling > Contact/helpdesk
number.
Operation manual
7
6
Troubleshooting
6.1
Symptom: You are feeling too cold (hot) in
your living room
Possible cause
The desired room temperature is
too low (high).
The desired room temperature
cannot be reached.
6.2
Symptom: The water at the tap is too cold
Possible cause
You ran out of domestic hot
water because of unusual high
consumption.
The desired DHW tank
temperature is too low.
7
Glossary
DHW = Domestic hot water:
Hot water used, in any type of building, for domestic purposes.
LWT = Leaving water temperature:
Water temperature at the water outlet of the heat pump.
EHBH/X04+08+16CA + EHVH/X04S18CA+EHVH/X08+16S18+26CA
Corrective action
Increase (decrease) the desired
room temperature.
If the problem recurs daily, do
one of the following:
Increase
(decrease)
the
room
temperature
preset
value.
Adjust the room temperature
schedule.
Increase the desired leaving
water temperature in accordance
with the heat emitter type.
Corrective action
If you immediately need domestic
hot water, activate the DHW tank
booster mode. However, this
consumes extra energy.
If you can wait, overrule
(increase) the active or next
scheduled desired temperature
so that more hot water will be
produced exceptionally.
If the problems recurs daily, do
one of the following:
Increase
the
DHW tank
temperature preset value.
Adjust
the
DHW tank
temperature
schedule.
Example:
Program
to
additionally
heat
up
the
DHW tank to a preset value
(Storage eco = lower tank
temperature) during the day.
Daikin Altherma - Low Temperature Split
4P313773-1 – 2012.05